Designation of opn on a single-line diagram

If for an ordinary person the perception of information occurs by reading words and letters, then for mechanics and installers they are replaced by alphabetic, digital or graphic symbols. The difficulty is that while the electrician completes his training, gets a job, and learns something in practice, new SNiPs and GOSTs appear, according to which adjustments are made. Therefore, you should not try to learn all the documentation at once. It is enough to gain basic knowledge and add relevant data as you work.

Introduction

For circuit designers, instrumentation mechanics, electricians, the ability to read an electrical diagram is a key quality and indicator of qualification. Without special knowledge, it is impossible to immediately understand the intricacies of designing devices, circuits and methods of connecting electrical units.

Symbols can be considered a special cryptographic code that explains the operation and principle of operation of a particular scheme. In Japan, the USA and Europe, icons differ significantly from domestic markings, which must be taken into account.

Types and types of electrical circuits

Before you begin to study the existing symbols of electrical equipment and its connections, you need to understand the typology of circuits. On the territory of our country, standardization has been introduced according to GOST 2.701-2008 dated July 1, 2009, according to “ESKD. Scheme. Types and types. General requirements".

  1. United.
  2. Located.
  3. Are common.
  4. Connections.
  5. Installation connections.
  6. Completely principled.
  7. Functional.
  8. Structural.

Among the existing 10 species indicated in this document, the following are distinguished:

  1. Combined.
  2. Divisions.
  3. Energy.
  4. Optical.
  5. Vacuum.
  6. Kinematic.
  7. Gas.
  8. Pneumatic.
  9. Hydraulic.
  10. Electrical.

For electricians, it is of greatest interest among all the above types and types of circuits, as well as the most popular and often used in work - an electrical circuit.

The latest GOST, which came out, has been supplemented with many new designations, current today with code 2.702-2011 dated January 1, 2012. The document is called “ESKD. Rules for the execution of electrical circuits” refers to other GOSTs, including the one mentioned above.

The text of the standard sets out clear requirements in detail for electrical circuits of all types. Therefore, when performing installation work with electrical circuits, this document should be used as a guide. The definition of the concept of an electrical circuit, according to GOST 2.702-2011, is as follows:

“An electrical diagram should be understood as a document containing symbols of parts of a product and/or individual parts with a description of the relationship between them and the principles of operation from electrical energy.”

Once defined, the document contains rules for the implementation on paper and in software environments of contact connection designations, wire markings, letter designations and graphic representations of electrical elements.

It should be noted that most often only three types of electrical circuits are used in home practice:

  • Mounting - for the device, a printed circuit board is shown with the arrangement of elements with a clear indication of the location, rating, principle of fastening and connection to other parts. Electrical wiring diagrams for residential premises indicate the number, location, rating, connection method and other precise instructions for the installation of wires, switches, lamps, sockets, etc.
  • Fundamental - they indicate in detail the connections, contacts and characteristics of each element for networks or devices. There are complete and linear circuit diagrams. In the first case, control, control of elements and the power circuit itself are depicted; in a linear diagram, they are limited only to the circuit with the remaining elements depicted on separate sheets.
  • Functional - here, without detailing the physical dimensions and other parameters, the main components of the device or circuit are indicated. Any part can be depicted as a block with a letter designation, supplemented by connections with other elements of the device.

Table 7

Name Designation
1. Covering lines:
1.1. Cover, general designation
1.2. Brick cover
1.3. Covering with ridge tiles
1.4. Covering with concrete slabs
1.5. Cover with profiled steel
1.6. Cover with plastic foil
2. Cable sewerage:
2.1. Sewerage in a pipe
2.2. Sewerage in P

pipes

2.3. Drainage in a cable block, for example, with three holes
Note. In the case of a large number of holes (more than three), the sign is drawn with three holes and the actual number of holes is expressed by the number given after this sign. For example, for a block with nine holes indicate
2.4. Sewerage in an open cable channel
2.5. Sewerage in a closed cable channel
2.6. Sewerage in a cable tunnel.
Note. If it is necessary to indicate the type of gasket, its designation is shown to the left of the cover designation, for example:
- underground line with brick cover
— underwater line covered with concrete slabs
- an underwater line laid in a pipe and covered with earth
3. Cable well
4. Cable cameras:
4.1. End chamber
4.2. Passage camera
4.3. Corner camera
4.4. Four-way camera
5. Cable shear protection
6. Protective anode
Note. About the conventional graphic symbols established in the table. 7, it is allowed to include clarifying data.

Designations of devices for monitoring pressure in the cable are given in table. 8.

Graphic symbols in electrical diagrams

  • 2.755-87 – graphic symbols of contact and switching connections.
  • 2.721-74 – graphic symbols of parts and assemblies for general use.
  • 2.709-89 – graphic symbols in electrical diagrams of sections of circuits, equipment, contact connections of wires, electrical elements.

In the standard with code 2.755-87, it is used for diagrams of single-line electrical panels, conventional graphic images (CGI) of thermal relays, contactors, switches, circuit breakers, and other switching equipment. There is no designation in the standards for automatic devices and RCDs.

On the pages of GOST 2.702-2011, it is allowed to depict these elements in any order, with explanations, decoding of the UGO and the circuit diagram of the difavtomat and RCD itself. GOST 2.721-74 contains UGOs used for secondary electrical circuits.

IMPORTANT: To designate switching equipment there is:

4 basic UGO images

UGOName
Closing
Breaking
Switching
Switching with neutral position

9 functional signs of UGO

UGOName
Arc suppression
No self-return
With self-return
Limit or travel switch
With automatic operation
Switch-disconnector
Disconnector
Switch
Contactor

IMPORTANT: Designations 1 – 3 and 6 – 9 are applied to the fixed contacts, 4 and 5 are placed on the moving contacts.

Table 1

Name Designation
1. line, track

General designation

Note. If it is necessary to distinguish in one diagram the lines being designed from those that are in operation, are subject to dismantling, or have been dismantled, then the following additional designations are used:
1. Designed line
2. The line is active
3. Line to be dismantled
4. Dismantled line
2. Crossing lines, routes
Note: If it is necessary to show the relative position in height of intersecting lines or routes, then the line or route located below is depicted with a break at the intersection
3. Radio relay line

Letter designations of gear types are given in table. 2.

Basic UGO for single-line diagrams of electrical panels

UGOName
Thermal relay
Contactor contact
Switch - load switch
Automatic - circuit breaker
Fuse
Differential circuit breaker
RCD
Voltage transformer
Current transformer
Switch (load switch) with fuse
Motor protection circuit breaker (with built-in thermal relay)
A frequency converter
Electricity meter
Normally closed contact with reset button or other push-button switch, with reset and opening by means of a special actuator of the control element
Normally closed contact with push-button switch, with reset and opening by retracting the control button
Normally closed contact with push-button switch, reset and open by pressing the control button again
Normally closed contact with push-button switch, with automatic reset and opening of the control element
Delayed closing contact that initiates upon return and operation
Delayed closing contact which only operates on return
Delayed closing contact which is only initiated when triggered
Delayed closing contact which is actuated by return and tripping
Delayed closing contact which only operates on return
Delayed closing contact that only switches when triggered
Timing relay coil
Photo relay coil
Pulse relay coil
General designation of a relay coil or contactor coil
Indication lamp (light), lighting
Motor drive
Terminal (separable connection)
Varistor, surge arrester (surge suppressor)
Arrester
Socket (plug connection):
  • Pin
  • Nest

Table 5

Name Designation
1. Intermediate double suspension
2. Hanging the wire (cable) on a cable
3. Wire (cable) self-supporting
4. Transposition of the line wire on the support
5. Transposition of the line wire between supports
6. Wire vibration damper
7. Capacitor bank on a support
8. Capacitor bank between supports
9. Pupinovskaya coil on a support
10. Control clamp on the support
11. Fuse on the support
12. Disconnector on support
13. Disconnector with fuse on support
14. Lamp on a support
15. Electro-acoustic devices on a support, for example, a loudspeaker
16. Lightning protection devices on a support:
16.1. Spark protection gap
16.2. Arrester. General designation
16.3. Ion arrester with fuse
16.4. Lightning rod
17. Safety mesh above the line
18. Safety mesh under the line

Designations of elements of underground lines are given in table. 6.

Designation of measuring electrical instruments to characterize circuit parameters

A heating element
UGOName
PFFrequency meter
PWWattmeter
PVVoltmeter
PAAmmeter

GOST 2.271-74 accepts the following designations in electrical panels for buses and wires:

Table 6

Name Designation
1. Pupinized cable.
Note. Near the conventional graphic designation, it is allowed to indicate the inductance of Pupin coils and the Pupinization distance, for example, a cable with Pupin coils with an inductance of 177 mH and a Pupinization distance of 1830 m
2. Cable couplings:
2.1. Straight end coupling
2.2. Branch end coupling
2.3. Linear coupling (connecting)
2.4. Linear coupling of increased reliability
2.5. Branch coupling with one branch (tee)
2.6. Branch coupling with two branches
2.7. Branch coupling with P

branches

3. Sealing sleeve, for example, for three cables
Note. The longer side is in the area of ​​high pressure.

Designations for the protection of underground and underwater lines are given in table. 7.

Letter designations in electrical diagrams

The standards for the letter designation of elements on electrical circuits are described in the GOST 2.710-81 standard with the text title “ESKD. Alphanumeric designations in electrical circuits." The mark for automatic devices and RCDs is not indicated here, which is prescribed in clause 2.2.12 of this standard as a designation with multi-letter codes. The following letter codings are accepted for the main elements of electrical panels:

NameDesignation
Automatic switch in the power circuitQF
Automatic switch in the control circuitSF
Automatic switch with differential protection or difavtomatQFD
Switch or load switchQS
RCD (residual current device)QSD
ContactorK.M.
Thermal relayF, KK
Timing relayKT
Voltage relayKV
Impulse relayKI
Photo relayKL
Surge arrester, arresterF.V.
fuseF.U.
Voltage transformerTV
Current transformerT.A.
A frequency converterUZ
AmmeterPA
WattmeterPW
Frequency meterPF
VoltmeterPV
Active energy meterP.I.
Reactive energy meterPK
Heating elementE.K.
PhotocellB.L.
Lighting lampEL
Light bulb or light indicating deviceH.L.
Plug or socket connectorXS
Switch or circuit breaker in control circuitsS.A.
Push-button switch in control circuitsS.B.
TerminalsXT

Graphic and letter symbols in electrical circuits

Just as it is impossible to read a book without knowing the letters, it is impossible to understand any electrical drawing without knowing the symbols.

In this article, we will look at the symbols in electrical diagrams: what types there are, where to find the decoding if it is not indicated in the project, how this or that element on the diagram should be correctly designated and labeled.

But let's start a little from afar. Every young specialist who comes to design begins either by folding drawings, or by reading regulatory documentation, or by drawing “this” according to this example. In general, normative literature is studied in the course of work and design.

It is impossible to read all the normative literature related to your specialty or even a narrower specialization. Moreover, GOST, SNiP and other standards are periodically updated. And each designer has to monitor changes and new requirements of regulatory documents, changes in the lines of electrical equipment manufacturers, and constantly maintain their qualifications at the proper level.

Remember Lewis Carroll in Alice in Wonderland?

“You have to run as fast as you can just to stay in place, and to get somewhere, you have to run at least twice as fast!”

This is not my way of whining about “how hard the life of a designer is” or boasting “look, what an interesting job we have.” That's not what we're talking about now. Given such circumstances, designers adopt practical experience from more experienced colleagues; they simply know how to do many things correctly, but do not know why. They work according to the principle “That’s the way it is here.”

Sometimes these are quite basic things. You know how to do it right, but if they ask “Why is this?”, you won’t be able to answer right away, referring at least to the name of the regulatory document.

In this article, I decided to structure the information regarding symbols, sort everything out, and collect everything in one place.

Representation of electrical equipment on plans

Despite the fact that GOST 2.702-2011 and GOST 2.701-2008 take into account this type of electrical circuit as a “layout diagram” for the design of structures and buildings, one must be guided by the standards of GOST 21.210-2014, which indicate “SPDS.

Images on the plans of conventional graphic wiring and electrical equipment.” The document establishes UGO on plans for laying electrical networks of electrical equipment (lamps, switches, sockets, electrical panels, transformers), cable lines, busbars, tires.

The use of these symbols is used to draw up drawings of electric lighting, power electrical equipment, power supply and other plans. The use of these designations is also used in basic single-line diagrams of electrical panels.

Conventional graphic images of electrical equipment, electrical devices and electrical receivers

The contours of all depicted devices, depending on the information richness and complexity of the configuration, are taken in accordance with GOST 2.302 on the scale of the drawing according to the actual dimensions.

Conventional graphic designations of wiring lines and conductors

Conventional graphic images of tires and busbars

IMPORTANT: The design position of the busbar must exactly coincide on the diagram with the place of its attachment.

Conventional graphic images of boxes, cabinets, panels and consoles

Conventional graphic symbols of switches, switches

On the pages of documentation GOST 21.210-2014 there is no separate designation for push-button switches, dimmers (dimmers). In some schemes, according to clause 4.7. the normative act uses arbitrary designations.


Conventional graphic symbols of plug sockets


Conventional graphic symbols of lamps and spotlights

The updated version of GOST contains images of lamps with fluorescent and LED lamps.

Conventional graphic symbols of monitoring and control devices

Table 4

Name Designation
1. Support, round support. General purpose
2. Square support
3. Rectangular support
Note: If necessary, it is allowed to use additional symbols (graphic, alphabetic, digital), indicating, for example, support material, design details, etc.
4. Support structures:
4.1. support with one stepson
4.2. Support with two stepsons
4.3. Support with guy
4.4. Pole with support
4.5. End support
4.6. Twin end support
4.7. Intermediate support
4.8. Intermediate support paired
4.9. A-shaped support
4.10. Portal support
4.11. Three-legged support
4.12. Four-legged support
Note: Around the graphical symbols set out in the table. 4, it is allowed to indicate support numbers.

Designations of elements and structures of overhead lines are given in Table. 5.

Graphic designation of SPD

The general view of SPDs for circuits is regulated in GOST R IEC 61643-12-2011 (Read PDF) “Surge protection devices in low-voltage power distribution systems. Principles of selection and application”, according to which the symbol looks like this (see image below):

Modern modular surge suppressors installed in electrical panels (ASU, ShchS, etc.), depending on the type, include other additional means of protection.

For example, both voltage and current limiting components are contained in a single package. In such cases, it is permissible to add markings of the corresponding controlled quantities to the standard schematic designation, for example, like this:

Also, often on diagrams where an SPD is used, a graphic designation of the main element on which it is built is shown - Varistor, Arrester or Gas-filled Arrester:

Each of the presented types of protection has its own pros and cons, therefore, information from a single-line diagram about what equipment is installed can be very important. Additionally, this is also indicated by marking the SPD on the diagrams with a letter code.

designation of a three-phase surge protector on the diagram

For three-phase SPDs, it is permissible to use the standard designation presented above, additionally indicating the number of connected conductors.

But there are diagrams in which three-phase SPDs are shown as three separate elements, for example varistors, combined in one housing. Both of these types are correct, but for convenience, simplicity and better readability of the drawing, it is better to use the first option.

Letter marking

There is no separate letter code for surge protection devices . Therefore, on single-line diagrams, it is customary to mark SPDs in accordance with GOST 2-710-81 (READ PDF) “Alphanumeric designations in electrical circuits” with two possible codes, depending on the main component used in a specific SPD model:

FV – on arresters

RU – on varistors

In the image below, an example of the correct designation of UZIP on a single-line diagram of a simple electrical panel:

The diagram shows a device in which, after the introductory two-pole circuit breaker, the neutral and phase conductors are connected, and the third terminal is connected to the protective grounding bus of the electrical panel PE.

Table 8

Name Designation
1. The partition in the cable is gas-tight or oil-tight
2. The valve in the cable is gas-tight or oil-tight
3. Bypass gas-tight or oil-tight partition
4. Tank for air or oil under pressure
5. Pressure gauge with alarm contacts
6. Low pressure alarm device

The designations of different devices are given in table. 9.