Step-by-step instructions on how to check and test a power transformer


Introduction

The main task of testing power transformers is constant monitoring of faults in all components of such equipment, their timely elimination after detection. All this is done with one goal - to continue the continuous operation of an important unit in the energy supply system for many energy consumers.

A series of tests allows us to assess how reliable, cost-effective, safe and technically sound a power generating unit is. To become more familiar with many electrical installation tests, detailed considerations of them using specific examples help. For example, a detailed description of the instructions on how to test a 250 kVA power transformer with a megger in this article is the most effective choice for such an acquaintance.

measuring the resistance of transformer windings to direct current

Measurement of the DC resistance of transformer windings is carried out in order to identify winding breaks and branches, poor contacts, soldering failures and detection of turn short circuits in coils. Winding resistance is measured by the bridge method or the voltage drop method.

Resistances up to 1 ohm are measured with a double bridge of the MD-6 type or a bridge of the R-316 type, which is also suitable for measuring resistances of more than 1 ohm. When measuring by the voltage drop method, the measurement circuit is also selected depending on the value of the measured resistance (Fig. 3). To avoid damage from extra currents, the voltmeter must be turned on when the current value is steady, and turned off until the current is turned off. Instruments used for measurement must have an accuracy class of at least 0.5. The current value during measurements should not exceed 20% of the rated current of the winding, so as not to introduce additional error into the measurements due to heating of the winding.

Resistances should be measured at steady temperatures; the temperature at which measurements were made must be measured and indicated in the test report. The linear resistance of all windings of the transformer is measured, and if there is a tap switch - at all its positions. Rice. 3. Measuring the resistance of a transformer winding to direct current using the voltage drop method a - for low resistances; b - for high resistances; B - rechargeable battery 6-12 V\ R - rheostat; K - button to turn on the voltmeter. The obtained values ​​must be compared with each other and with factory test data. When comparing resistance values, they must be brought to the same temperature using the formulas: for windings made of copper wire; - for windings made of aluminum wire, where R2 is the resistance brought to temperature 4; Ri is the resistance measured at temperature t1.

The resistance values ​​of individual phases of the transformer should not differ from one another and from the factory data by more than 2%. If the discrepancy with the factory data exceeds 2%, but is the same for all phases, you should look for an error in the measurements.

Why do you need to test transformers?

The power transformer is an important transmission unit as part of a powerful and complex power system that provides power to a significant number of industrial and household energy consumers. Such a unit must be reliable and serviceable for a long time, so that there is no failure in the useful work of industrial consumers, and there is no shortage of electricity consumption in the everyday life of ordinary people.

That is why oil and dry power voltage converters are constantly tested:

  • At manufacturing plants, numerous inspections and performance tests are carried out - in order to guarantee that a complex technical device for converting voltage from one class to another after manufacturing is fully operational and ready for further work at the site;
  • When installing a supply system in an ensemble, testing according to a special acceptance testing methodology - in order to understand that during the transportation and subsequent installation of power equipment, no defects or installation errors occurred or were created that would not be able to provide proper, stable power to the required number of consumers;
  • Periodically during the operation of electrical installations and components, as a result of which certain failures or defects of complex transmission equipment may also occur - to prevent pre-emergency or emergency conditions. To identify defects at early stages and timely eliminate them in operational mode with minimal losses for all energy consumers.

Such monitoring and checks of the operation of power transmission devices ensure maximum quality of operation of power systems as a whole, which means that the maximum quantity and quality of electricity is obtained in industry and in the domestic sector, which has a beneficial effect on the level of their efficiency.

Measuring winding capacitance at various frequencies.

The degree of humidification of the transformer windings can also be determined by measuring their capacitance at different frequencies (capacitance-frequency method). The capacitance of the windings is measured at a frequency of 50 Hz (C50) and at a frequency of 2 Hz (Cg) with a special humidity control device of the PKV type on a transformer filled with oil, between each winding and the housing with the free windings grounded. Before measurement, the winding under test must be grounded for 2-3 minutes. The more humidified the insulation of the transformer windings is, the greater the C2/C50 ratio. It also increases with increasing temperature of the transformer windings, so measurements are made at a winding temperature of 10-30 ° C. The value of the C2/C50 ratio also depends on the dielectric loss tangent (tan b) of the oil poured into the transformer: with an increase in tg b oil, the C2 ratio /C50 increases. For transformers with voltage up to 35 kV inclusive and power less than 10 MVA, the value of C2/C50 windings at different temperatures should not exceed the following values: Winding temperature in ° C 10 20 30 Ratio C2/C5o 1.1 1.2 1.3 Tangent measurement dielectric loss angle (tg6). Moistening of the transformer winding insulation, as well as a number of other defects, lead to an increase in dielectric losses and, as a consequence, to an increase in the dielectric loss tangent (tg6). Rice. 2. Schematic diagram of the MD-16 bridge (inverted) Tn - test transformer; Cx—test object; CD, - is a model capacitor; G - galvanometer; R2 - variable resistance; Rt - constant resistance; C - container store; E - screen; R - spark gap

Measurement of tg b is carried out using an alternating current bridge type MD-16. Typically, the so-called “inverted” bridge circuit is used (Fig. 2), which allows measurements to be made without removing the inputs from the transformer. Measuring the dielectric loss tangent is mandatory for transformers with a voltage of 35 kV, but can also be carried out for transformers of a lower voltage class if the results of other measurements cannot give a final conclusion about the state of the insulation. The dielectric loss tangent is measured at a temperature not lower than +10 ° C on transformers filled with oil, at an alternating current voltage not exceeding 60% of the factory test voltage, but not higher than 10 kV. The tangent of the dielectric loss angle in the transformer insulation depends on tg6 of the oil poured into the transformer. With an increase in oil tg6, itg6 of the windings increases. The value of tg6 insulation of the transformer windings should not exceed the values ​​​​given in table. 2. Table 2

Transformer power and voltage class of HV winding in % AT winding temperature in e C
10 20 30 40 50 60 | 70
Up to 35 kV inclusive with a power of less than 2,500 kVA 1,5 2 2,6 3,4 4,6 6 8
Up to 35 kV inclusive with a power of less than 10,000 kVA 1,2 1,5 2 2,6 3,4 4,5 6

The tg 6 values ​​indicated in the table apply to all windings of a given transformer. The tg6 value during installation should not exceed 130% of the value specified in the factory test report. The values ​​of tg6 measured at the factory at temperature t2 lead to the measurement temperature at installation by dividing by the coefficient K2. Temperature conversion factor values

Temperature difference tz—tiB °С 5 10 15 20 25 30 35
Kz coefficient value 1,15 1,31 1,51 1.75 2 2.3 2,65
Temperature difference іг - ti in °С 40 45 50 55 60 65 70
K coefficient value, 3 3,5 4 4.6 5.3 6.1 7

Oil sampling. An oil sample is taken from the bottom of the tank at a temperature of the sampled oil not lower than + 5°C. The container in which the sample is taken must be clean and well dried. The selected oil is subjected to a short laboratory analysis for the absence of moisture, the content of mechanical impurities, the reaction of aqueous extract and determination of the acid number. In addition, the electrical strength of the oil is determined using devices such as AMI-60 or AII-70 in a standard spark gap. The breakdown voltage of the oil must be not lower than 25 kV for transformers with voltages up to 15 kV inclusive and not lower than 30 kV for transformers with voltages up to 35 kV inclusive.

Methodology for acceptance testing of power transformers

Work on commissioning a new power plant, which includes one of the main power units - a power voltage transformer - must take into account a certain testing methodology for all its components and mechanisms. Acceptance tests of power transformers on new energy systems or at the time of scheduled preventive maintenance of already operating energy facilities include up to 20 types of various checks and control tests depending on the type of transformer according to voltage class, the difference in its cooling systems, and other complexity of other systems electricity supply

Also, it is important to understand the technical conditions for power transformers according to GOST.

To begin with, a review of the general provisions for testing power electrical equipment allows us to understand their details.

General provisions

Power transformers are subject to control checks and tests to identify possible defects when commissioning new equipment or determining the degree of reliability of operating electrical units according to a strict schedule of their frequency and following a certain amount of testing:

  • A mandatory preliminary determination of the conditions for connecting the transformer without drying is carried out;
  • The DC resistance of the transformer windings is measured;
  • Resistance measurements are carried out, tests are carried out with increased voltage of industrial frequency insulation of windings, insulation of structural elements;
  • Transformer oil is tested;
  • Tank leak testing;
  • The transformation ratio is checked, winding connection groups, all switching equipment and devices, cooling systems, safety systems in the form of numerous transformer valves are tested, and the suitability of exhaust pipes is assessed.

Types of checks

Based on the listed provisions for testing power power equipment, it becomes clear to an ordinary person unfamiliar with power supply how comprehensively such a power unit is checked for serviceability and performance. If transformers have high voltage conversion powers from 1000 kVA to tens of mVA, type tests are added to their testing:

  • Measurements of the percentage of dielectric losses - for power equipment designed for voltages of 35 kilovolts;
  • Measurements of current and no-load losses - for transformers with a power of 1000 kVA and above;
  • Short circuit resistance measurements - for transformers with a power of 63 mVA and above.

When carrying out all of the above tests and tests, the working personnel must be guided by certain regulations, instructions and regulatory documentation for carrying out such work in accordance with safety regulations and environmental protection.

Normative references

General technical requirements for power converting devices of various voltage classes are determined by the following standards:

  • “PUE” (“Rules for Electrical Installations”), 7th edition, chapter 1.8, paragraph 1.8.16, paragraphs 1-14;
  • “PTEEP” (“Rules for the technical operation of consumer electrical installations”), Appendix 3 Section 2; Appendix 3.1, table 5;
  • Transformer passport from the manufacturer;
  • GOST 11677-75 - in the standard, which describes programs and acts of acceptance, standard and periodic tests of transforming electrical equipment carried out at manufacturing plants;
  • GOST 3484-77 / GOST 22756-77 / GOST 8008-75 – standards that include and regulate the entire methodology for ongoing testing before and after installation of power systems at sites.

At the time of testing, it is worth additionally being guided by several more regulatory documents such as GOST 1516 / STP 09110.220.366-08, which help specialists determine the detailed scope of testing and verification work on power voltage transformers in accordance with safety and environmental protection requirements.

Measurement methods

Guided by the above documentation, the following methods of measuring components and mechanisms are carried out at the time of testing power transformers:

  • Measuring the insulation resistance of transformer windings - this process is carried out using a megohmmeter with a rated operating voltage of 2500 volts. Before and between measurements, all transformer windings must be grounded;
  • The dielectric loss tangent is measured using an AC bridge. If the tested transformers are oil-filled during this period, the measurement is carried out at a supply voltage lower than the nominal nominal voltage, equal to 2/3 of it;
  • Measuring winding capacitance is referred to as electrical testing of a transformer, which allows one to obtain data on the degree of humidity of the transformer windings. This type of measurement is available when monitoring the transformer absorption coefficient, which is the ratio of the insulation resistance of the windings after a sixty-minute measurement to the resistance value after a fifteen-minute measurement;
  • Measuring the resistance of windings to direct current is a method that allows you to check power transformers for hidden faults;
  • The transformation ratio of power equipment is determined by the method of two voltmeters, which gives an understanding of the correct or incorrect connection of a group of transformer windings.

Additional tests

There are other periodic tests of the power transformer, which are in the nature of additional tests and checks of voltage transformation devices. These include:

  • Checking phasing, inputs and built-in current transformers of power equipment;
  • Switching on the device to the rated voltage with a push and others.

Both for basic measurement methods and for additional tests, there are special measuring instruments defined by regulations, conditions for their implementation, permissible error correction factors and a certain clear procedure. The article briefly and succinctly introduces all this below.

Measuring

Or the instruments used to carry out the acceptance testing procedure include the following standard set of electrical equipment:

  • Electronic megohmmeter for a voltage limit of 2500 Volts (type F4102/2-M);
  • Voltmeters (type E545);
  • Ammeter (type E526);
  • DC bridges;
  • Laboratory testing facility or stand (type P333);
  • Other instruments used in experiments depending on the type of techniques being performed.

At the time of testing, it is impossible to do without certain means of protection for the working personnel conducting tests and trials of dangerous electrical equipment in the form of:

  • Portable grounding;
  • Dielectric carpets, gloves, boots;
  • Warning posters.

Only after ensuring complete safety and having carried out a full range of preparatory and organizational work should one begin the current processes of testing power voltage transformers.

Accuracy Requirements

The regulations for testing power transformers establish certain requirements for measurement errors, without taking into account which during testing it is possible to make a number of technical errors in further calculations of the values ​​of test methods for electrical equipment, which in turn will lead to incorrect final conclusions about the degree of reliability of the transformer and its performance in further operation .

The error in all types of tests and measurement methods should not exceed more than 5% of the established nominal values.

Conditions

The methodology for testing and testing such a complex technical device involves the selection of certain climatic conditions for carrying out, preparatory, organizational and technical preliminary work. They include the following conditions:

  • Any methods of measuring voltage transformer systems are carried out only in dry weather conditions;
  • Before testing, the power unit itself must be pre-tired, all places of proposed measurements must be cleared of dust and have free access for the personnel being tested;
  • All necessary testing instruments must contain current verification dates and be in full working order;
  • Tests for measuring the resistance of windings to direct current are carried out using a laboratory tool - an ohmmeter of appropriate ratings. In the method, it is necessary to set the value of the constant frequency current to 20% of the winding current. The resistance of the wire in the measurement circuit should not exceed 0.5% of the voltmeter resistance value;
  • Mandatory demagnetization of the magnetic circuit from any residual magnetization is used for the purity of measurements of current and no-load losses of the transformer;
  • If the transformer under test has just arrived from the manufacturer and has not previously been in operation as part of the power system, measurements of its no-load losses are carried out first;

More details about the remaining conditions for testing transformers can be found in the regulatory documentation that defines the methods for conducting them and testing the transforming electrical system.

Procedure for conducting inspections

The regulations and test procedure regulations specify a strict procedure for conducting tests of a power voltage transformer. It begins with establishing the conditions for turning on the transformer.

Defining trigger conditions

Whether it is possible to turn on the transformer without drying is determined directly at the time of testing, following standards such as RTM 16.800.723-80 (“Power transformers. Transportation, unloading, storage, installation and commissioning”). Conclusions about the switching conditions are formed based on the data specified in the equipment passport from the manufacturing plants, understanding which of the four power and voltage class groups the tested power unit belongs to, and also taking into account the actual transportation conditions of the transformer.

Insulation resistance measurement

Measurements of the insulation resistance of power transformers using acceptance testing technology are carried out before measuring the dielectric loss tangent and measuring winding capacitances. Measurements are made using a megohmmeter with a rated voltage of 2500 volts and a resistance limit on the scale of 10,000 ohms. Before starting resistance measurements, the windings under test must be grounded for at least three minutes.

This test allows you to determine the presence of hidden faults in power equipment and calculate the degree of moisture in objects. The resistance of the windings should be measured at the same temperature, at different time intervals - 15 and 60 seconds after applying voltage to the test object.

How to measure transformation ratio

Determining this parameter during testing allows you to check the correctness of the passport values ​​of the transformation ratio from the manufacturer's supplier, in addition, this stage of testing provides an understanding of the correct connection of the winding branches connected to the switching devices of power equipment.

The test is carried out at all switching stages, the value of the coefficient should not differ by more than 2% from the values ​​​​specified in the power transformer passport.

In practice, the measurement of the transformation ratio is carried out using the method of two voltmeters. The essence of this method is to apply a nominal voltage to one of the windings of the transformer and connect two voltmeters in parallel to this circuit, measuring the voltage value supplied to the winding and its value on the second winding of the transformer.

An important point in such a measurement is the need to control the supply voltage to the transformer winding in the range of at least 1% of the nominal nameplate value, without any distortions.

After measuring the phase and linear voltage values ​​on the winding of a three-phase transformer, using special formulas specified in the test regulations, the value of the transformation ratio is calculated and the resulting value is compared with the value of the transformation ratio from the equipment’s factory passport.

How to measure DC winding resistance

Tests are necessary to identify defects in winding wires, switching devices, and all contact connections of transformer windings. Before carrying out the test, all contact parts to be measured must be thoroughly cleaned of dust and dirt.

The test is carried out on all branches of transformer windings having switching devices without excitation.

Measurements begin only after at least three complete switching cycles have been completed on the power transformer.

The resistance values ​​of the windings on all branches of different phases should differ from the passport values ​​by no more than 2% at the same temperature. If it is necessary to carry out additional temperature recalculations, the results obtained should vary by 5% from the original ones.

Testing the resistance of windings to direct current can be carried out using two methods:

  • Voltage drop method - the simplest test method using simple measuring instruments (voltmeters and ammeters) is based on measuring the voltage and current drop values ​​in the test area, and after calculating the resistance value according to Ohm's law and comparing it with the transformer's nameplate data;
  • The bridge method is a more technically complex method, which requires the use of a measuring stand of a device (type RET-MOM). In this case, measurements are made of the active resistance of the transformer windings at different voltage values, and the results are compared with the ratings of the equipment passport from the manufacturer.

The second method of measuring resistance is more complex and requires the mandatory use of special equipment being tested, qualified, trained personnel and other parts at the time of testing, but it allows for a broader and more accurate test and determination of the suitability of power equipment.

Phasing

In simple words, this is a check for the coincidence in phases and value of secondary voltages at all terminals of newly commissioned new power transformers in a single voltage transformation system or in power installations that use a second backup supply input, and therefore a second transformer. Their inputs and outputs must be in phase in a closed circuit

It is for this purpose that these tests are carried out, with the obligatory finding of a common test point in the circuit under test. In practice, on high-voltage bushings, checking the correct phasing is done using temporary jumpers and operating rods; on low-voltage bushings, measuring the voltage with voltmeters.

Idle speed measurement

The essence of the tests is quite simple. According to the diagram given in the "PUE" for two voltage values ​​- nominal and small - the no-load current is measured using a phase meter. Using its obtained value, calculation formulas are used to calculate the active power consumption, which will be the value of the no-load losses of the voltage transformer being tested.

The values ​​of no-load losses obtained by testing, equal to the equivalent of the active design no-load power, are compared with the manufacturer's nameplate ratings in these test criteria. For idle speed measurements they must not exceed certain values ​​expressed as a percentage:

  • With a single-phase test, the results should not exceed 10% of the passport values;
  • For three-phase tests – no more than 5%.

The data from this test, as well as those described above, after it has been carried out and calculations have been carried out, are recorded in protocols and test reports for electrical equipment.

Short circuit

The tested power transformer is subjected to a short circuit test in order to check the secondary winding circuit, obtain the rated current value in this circuit, the value of power loss, and obtain data on the voltage drop across the internal resistance of the power unit.

Short circuit testing is carried out by creating a short circuit (an artificial type according to the diagrams from the PUE standards) of the secondary winding circuit and the rated current of the primary winding of the transformer. To carry out such a test, measuring instruments such as ammeter, voltmeter, wattmeter are used, connected according to the circuits for their inclusion in a special experimental circuit.

Control tests begin at zero voltage at the transformer input. Gradually increasing the voltage of the primary winding to a certain value, with the current in the primary winding reaching the nominal value.

After receiving the measurement results of the devices, they are compared with the passport ratings from the manufacturer. Practical data should be within 5-10 percent deviation in value from the passport data.

Processing, evaluation and presentation of results

In the process of conducting control tests of new or previously operated power voltage transformers as part of various energy systems and facilities, a special protocol is maintained - a work log in which the tested personnel records, certifies and endorses all the data obtained by experiments, measurements, calculations based on the formulas prescribed by the regulatory documentation for acceptance testing methodology.

After completing all the main experiments and entering the data into the specified log, on their basis, taking into account the values ​​and data of past tests of power energy equipment, an assessment and analysis of the further performance of the tested sample or other actions related to possible repair work of the equipment is carried out.

Based on the assessment and analytical activities, the maintenance personnel makes final conclusions and makes an opinion on the power equipment, which they record in the protocols (insulation cards) for testing and experiments.

Entering the findings into the test report is the final step of the entire methodology for acceptance testing of a power voltage transformer at a specific facility.

Safety and environmental requirements

It is important for personnel conducting tests and laboratory experiments and measurements on power energy equipment to comply with mandatory safety and environmental protection requirements. Mandatory implementation of all safety measures for testing high-voltage equipment of increased danger is regulated by the standards specified in “POT”, “PPB”, and labor protection instructions. Operating personnel must know and practice these requirements.

The testing methodology for power transformers does not pose any environmental hazard to the environment.

Diagnostics of household step-down transformers

Such elements are contained in power supplies that reduce the voltage at the 220 V input to a value of 5–30 V at the output. Before checking the operation of a step-down transformer, you must first make sure that its primary winding is in good condition. If a burning smell, smoke or crackling occurs, measurements must be stopped. If the described defects are not identified, measurements are performed on secondary coils. During the measurement process, it is permissible to touch them only with the probes of the tester. Measurement data is compared with control data. If the discrepancy is 20% or more, a winding fault is confirmed. But it will be possible to test such a block only if there is a 100% identical working block, which is necessary to assemble the control data. When working with a resistance of about 10 Ohms, the results may be distorted (typical of some testers).

Additional tests

Tests assessing the external integrity of the transformer housing, analysis of transformer oil, bushings, testing of built-in current transformers of a power voltage converter, although they are of an auxiliary nature, must be carried out without fail during acceptance and delivery work at the facility.

Each of them is briefly described below.

Transformer oil

Oil in the power voltage transformer system plays the role of a cooling, insulating liquid, depending on the type of assembly of the electrical unit. In addition, over time, the necessary indicators of this liquid substance may change (the oil may “age”), which can negatively affect the proper operation of the entire voltage converter as a whole. Therefore, during additional tests, transformer oil is evaluated according to several parameters:

  • The degree of possible oxidation of the oil;
  • Critical heating to the point of liquid ignition;
  • Density tolerances of the substance.

Data is collected on the basis of tests using special laboratory meters, which after testing are compared with the passport values ​​and in case of serious deviations of the obtained parameters from the specified ones, appropriate measures are taken.

Vvodov

The next auxiliary test is to check and inspect all contact inputs of power equipment to detect obvious faults, deformations or other defective changes that were not present at the stage of previous testing.

It is mandatory to clean the contact inputs from dust, dirt and other foreign substances that may adversely affect the performance of the equipment.

Built-in CTs

The built-in current transformers on the power voltage converter are subject to additional mandatory testing in accordance with the “PEU” point by point. 7.1, 7.3.2, 7.4-7.6. These tests include several hardware checks:

  • Measuring the insulation resistance of built-in CTs - the resulting resistance value must be at least 1 MΩ;
  • Thermal imaging control of TT – test and assessment is carried out in accordance with the standards specified in Appendix 3 “PUE”;
  • Insulation monitoring under operating voltage.

All obtained parameters, after their comparative analysis with the passport data, are added to the main results of the equipment check by recording in the work log.

Inrush switching to rated voltage

Before testing a transformer with such an experiment, installation and cleaning work with power equipment must be completely completed. The primary analysis and general measures of the transformer test methodology must provide at least satisfactory values ​​and parameters for performing inrush switching at the voltage rating.

The essence of the auxiliary test is to connect a diesel generator to the transformer and apply voltage to it without load in 3-6 times the magnitude of the push in the presence of working personnel who evaluate and analyze all the protections and mechanisms of the power voltage converter.

If the transformer protections were not triggered to disconnect from the network, the equipment remains energized for a long period with further “wiretapping” and analysis of its operation.

Based on the testing results, the data obtained and conclusions about the operation of power electrical equipment are entered into the working test log.

Monitoring the circuit under load - direct method

This method is used to check the operating parameters of the converter. Its essence is to determine the currents in the windings under load. A load is connected to the secondary winding such that the currents flowing in the windings are at least 20% of the rated values. If there are several secondary windings, those not connected to the load must be short-circuited. This is for safety reasons to avoid high voltage in the open secondary coil. The obtained values ​​are divided among themselves, and the transformation coefficient is determined. If it corresponds to the rated value, the serviceability of the device is confirmed; if it does not, the defect must be determined.

Instructions on how to check a 250 kVA transformer with a megohmmeter

In detail, the test for checking the insulation resistance of the windings of a power transformer with a rated power of 250 kVA, regardless of the voltage class on the high-voltage side (6/10 kV or higher) and the voltage value on the low-voltage side equal to the standard 0.4 kV, is carried out in several clear steps, which allows you to perform such the test is most complete, correct and most importantly safe.

The main safety requirement in the instructions for checking a 250 kVA transformer or any other power with a megohmmeter is carried out by the working personnel only together, with the electrical safety group of the person conducting the measurement not lower than IV (up to and above 1000 volts), and his partner - not lower than III electrical safety category.

Resistance measurements are carried out no earlier than 12 hours after filling the unit with transformer oil to the nominal level. Measurements are carried out at an insulation temperature of at least 10 degrees Celsius.

Subsequence

The sequence of the test-measurement of insulation resistance with a 2500V megohmmeter and a resistance limit of 10000 Ohms is as follows:

  • Carrying out an external inspection of the voltage converter as part of the power system - before testing, specialists must conduct an external inspection of the equipment and visually verify the integrity of all elements, the absence of damage to the transformer radiator, insulators, oil level, thermometer glass, transformer grounding;
  • Measurement of megohmmeters (2500 V/10000 Ohm) is carried out in strict sequence according to the diagrams from the regulatory documentation for the current test:
  • NN – VN;
  • VN – NN;
  • VN + NN.

In this case, all terminals of the windings of the same voltage are connected to each other, the remaining windings are necessarily grounded.

  • Using a megohmmeter connected to the terminals of the windings, two resistance measurements are taken with a time interval of 15 and 60 seconds. The starting point is taken from the beginning of rotation of the device handle. Before starting the tests, all windings of the transformer must be grounded for at least 5 minutes;
  • Before carrying out measurements, the working area where the unit under test is installed must be cleared of any foreign objects, fenced off, and electrical safety posters such as “STOP! VOLTAGE!”, and at switching points or other moving contacts there are warning signs “DO NOT TURN ON! PEOPLE WORK!”
  • The obtained winding resistance values ​​in equal temperature equivalent, but with different time intervals, are compared with the standard data of transformers from the technical literature, and recorded in the working test log. The resistance rating of the windings according to the paragraphs of the “PUE” in the normal mode of the device is not less than 0.5 MΩ;
  • After resistance measurements, the following measurements are taken as part of this type test:
  • Measuring the resistance of tie rods, bandages, and other structural fastening elements of the equipment body relative to the active metal of the magnetic circuit and windings;

Final stage

The obtained values ​​are recorded in the same format in the work log, and then analyzed with the main resistance values. A megohmmeter with a voltage rating of 2500 Volts and a resistance limit of 10,000 Ohms allows not only to obtain data on the resistance values ​​of the internal elements of a transformer of 250 kVA, but also makes it possible to test them for integrity inside, thereby determining whether there are faults inside the transforming device that are necessary for urgent troubleshooting or repair. Which in turn influences the final conclusions about the possibility of putting new or previously used equipment into operation as part of the entire complex electrical installation.

Insulation resistance measurement.

The insulation resistance between each winding and the housing and between the windings of the transformer is measured with a megger for a voltage of 2500 V. To eliminate the influence of leakage currents on the surface of the insulators, especially when taking measurements in humid weather, screen rings made of bare copper wire are applied, connected to the “screen” clamp of the megohmmeter (Fig. 1). Before starting to measure the insulation resistance, the tested winding of the transformer is grounded for 2-3 minutes and the surface of the inputs is thoroughly wiped. Megger readings are taken 15 and 60 seconds after the handle begins to rotate, which corresponds to the values ​​of R15 and R60. The megger handle should be rotated evenly at a speed of 110-120 rpm. It is advisable to use a megohmmeter with a motor drive type PM-89 or with a kenotron rectifier attachment. These measurements are also used to determine the absorption coefficient, i.e. the ratio R15 / R60, which is one of the indicators of the degree of winding humidification. For a transformer with a voltage up to 35 kV inclusive, a power of less than 10 MVA at different winding temperatures, the insulation resistance value must be no less than the specified values: Winding temperature in °C. 10 20 30 40 50 60 70 R60 in Moi. 450 300 40 The measured value of insulation resistance is compared with the value of insulation resistance according to the manufacturer (according to the factory test report). Before comparison, the R60 value measured at the factory is converted to the installation measurement temperature by multiplying by the conversion factor K1.

Rice. 1. Measuring the insulation resistance of transformer windings with the application of screen rings The value of the K\ coefficient depending on the temperature difference during factory tests (f2) and during installation measurements (t\): The insulation resistance at installation must be at least 70% of the insulation resistance according to the data factory test report. Absorption coefficient value R60/R15. It should be no lower than 1.3 at a temperature of 10-30° C.

Test voltage table

Tabular data for power transformers are given in the “PUE” in the table of rules No. 1.8.11. Tests with increased voltage of industrial frequency are carried out to insulate transformer windings and inputs of power electrical equipment. The time standard for these tests is set at an interval of 1 minute.

Table 1.8.11 for “PUE”. Industrial frequency test voltage of internal insulation of power transformers and reactors with normal insulation and transformers with lightweight insulation (dry and oil-filled)

Winding voltage rating, kVTest voltage in relation to the housing and other windings, for insulation, kV
Type – normalType – lightweight
< 0,694,52,7
316,29
622,514,4
1031,521,6
1540,533,3
2049,545
3576,5
110180
150207
220292,5
330414
500612

Each of the windings is subjected to an increased voltage test for 1 minute. At this moment, the remaining windings, all contact parts and other current-carrying elements of the transformer are carefully grounded.

Measurement of the AC/C ratio.

One of the methods for measuring the humidity of windings is the “capacity-time” method, which measures the increase in capacitance (AC) to capacitance (C) over a certain period of time. The ratio of these values ​​(A C/C) characterizes the degree of moisture in the insulation of the transformer windings: with increasing humidity, the ratio A C/C increases. The A C/C ratio is measured with a special device, type EB-3, on transformers not filled with oil. Typically, these measurements are made at the beginning of the transformer inspection, after lifting the removable part and at the end of the inspection, before immersing the transformer core in oil. The A C/C ratio is measured for each winding with free windings connected to a grounded frame. Before measurement, the winding under test is grounded for 2-3 minutes. The wires connecting the device to the winding under test should be as short as possible. Table 1

Power and voltage class of the high voltage winding (HV) Temperature in C
10 | 20. 30 40 50
Up to 35 kV inclusive with a power of less than 10 MVA D S/S ratio at the end of the audit in % 13 20 30 45 75
The difference between the value of A C/C at the end and beginning of the audit in % 4 6 9 13,5 22

The value of the A C/C ratio in %, measured at the end of the audit, and the difference in % between the value of D C/C at the end and beginning of the audit should be within the limits given in table. 1. The value of the L C/C ratio increases with increasing temperature. Therefore, if during the inspection of the transformer the temperature of the removable part has changed and measurements of the D S/C ratio at the end and beginning of the inspection were made at different temperatures, they must be brought to the same temperature before comparison. Recalculation of the value D C/C, measured at the end of the inspection at temperature t\, to the winding temperature at the beginning of the inspection t2 is done by multiplying by the temperature conversion factor K2 Values ​​of the temperature conversion factor Measurement of winding capacitances at different temperatures. The capacity of moistened insulation increases with increasing temperature much faster than the capacity of non-moistened insulation, therefore, by the ratio of the capacitances of transformer windings measured at different temperatures, one can judge the degree of moisture in their insulation. Capacity is measured on a transformer filled with oil using an alternating current bridge type MD-16, and in its absence for transformers with a power of less than 10 MVA, voltage up to 35 kV using the ammeter-voltmeter method. Winding capacitance is measured when the transformer is heated to a winding temperature of at least 70° C (Cburn) and at a temperature 50° C lower (Chol). The value of the Stor/Shol ratio for transformers with a power of less than 10 MVA and voltage up to 35 kV inclusive should not exceed 1.1.

determination of transformation ratio

The transformation coefficient is determined for transformers after their overhaul with the change of windings, imported and without a passport. The transformation ratio of a transformer is the ratio of the voltage on the high-voltage (HV) winding to the voltage on the low-voltage (LV) winding at no-load: where CT is the transformation ratio; Ui is the voltage on the HV winding; U2~ voltage on the LV winding. The transformation ratio is determined on all winding branches available for switching and for all phases. For three-winding transformers, it is sufficient to check the transformation ratio for only two pairs of windings. Measurements are made using the method of two voltmeters (Fig. 4). Voltage is supplied to the HV winding. For low-power transformers, the input voltage should be 20-30% of the rated voltage, and for high-power transformers 1-5% is sufficient. When testing three-phase transformers, a symmetrical three-phase voltage is applied to one winding and the voltage is simultaneously measured between the corresponding line terminals of the same name of both windings being tested. In the absence of three-phase symmetrical voltage, the transformation ratio can be determined with single-phase excitation, if it is possible to measure phase voltages, as well as for transformers in which at least one winding is connected in a “triangle”. The transformation ratio is measured by alternately short-circuiting one of the phases according to the diagrams shown in Fig. 5, a, b, c. The transformation coefficient with this method will be equal to 2/Сф (with the Y/D scheme) or /Сф/2 (with the D/Y scheme), where Кф is the phase transformation coefficient. If there is a zero point in the star-connected winding, then the transformation ratio can be measured without shorting the phases according to the diagrams shown in Fig. 6 a, b, c. In this case, the phase transformation ratio is measured directly. For measurements, you should use instruments with an accuracy class of at least 0.5. Rice. 4. Measuring the transformation ratio of a transformer The measured transformation ratio should not differ by more than 1-2% from the transformation ratio on the same branch on other phases and from the transformer’s rating data. Rice. 5. Phase-by-phase measurement of the transformation ratio of a three-phase transformer with single-phase excitation with phase short-circuiting

Rice. 6. Phase-by-phase measurement of the transformation ratio of a three-phase transformer with single-phase excitation without phase short-circuiting

CHECKING THE WINDING CONNECTION GROUP

Rice. 8. Checking the connection group of the windings of a single-phase transformer using the DC pulse method. This check is also carried out for transformers that have undergone a major overhaul with a change of windings, imported and without a passport.

Rice. 7. Checking the connection group of the windings of a three-phase transformer with a phase meter - phase meter; U - rheostat B - battery or accumulator 2-12 e; K - button; G - galvanometer with zero in the middle of the scale

The winding connection group characterizes the angle between the voltage vectors of the HV and LV windings of the transformer phases of the same name. Checking the winding connection group can be done using several methods. Phase meter method. With this method, the series winding of a single-phase phase meter is connected through a rheostat to the terminals of one of the transformer windings, and the parallel winding is connected to the same terminals of the other winding of the transformer (Fig. 7). A reduced voltage sufficient for the operation of the phase meter is supplied to one of the windings, and the rated current in the series winding of the phase meter is set with a rheostat. The phase meter shows the angular displacement of voltage vectors in degrees. To avoid possible errors in measurements, it is better to use a phase meter with a four-quadrant scale of the E-500 type. For three-phase transformers, it is recommended to repeat measurements on two pairs of terminals. For example, AB-ab and AC-ac - in both cases the results should be the same.

Direct current pulse method.

Determination of the connection group of transformer windings by this method is carried out using a galvanometer with a zero in the middle of the scale or a magnetoelectric voltmeter. For single-phase transformers, the test diagram is shown in Fig. 8. DC voltage 2-12 V from a battery or accumulator is supplied to terminals A - X of the high voltage winding. If, when the current is turned on, the polarity of terminals a-x turns out to be the same as the polarity of terminals A-X, then the connection group of the windings of this transformer is 12, otherwise - 6. For three-phase transformers, the group is determined according to the diagram (Fig. 9), where the deviations of the galvanometer needle compiled for the case of connecting windings according to the Y/Y circuit - group 12. With the polarity of connecting the direct current source and galvanometer indicated on the diagram, deviations of the arrow to the right (when the current is turned on) are indicated by a plus (+), deviation of the arrow to the left is indicated by a minus (-). For odd-numbered connection groups, zero galvanometer readings occur. Deviations of the galvanometer when checking the most common groups of winding connections are given in table. 4. The test results are recorded in the same form and, based on the coincidence of the readings with the data in the table, the connection group of the windings of the transformer being tested is established.

Rice. 9. Checking the connection group of the windings of a three-phase transformer using the DC pulse method

Table 4

Group 12 6 11 1
Phases - ab be sa ab be sa ab be sa ab be sa
A-B. . . + _ + + + 0 _ + 0
B—C. . . + + + + 0 0 +
S—A. . . + + + 0 + 0 +

measurement of no-load current value

To measure the no-load current, the rated voltage is supplied to the low-voltage winding with the other windings open. For three-phase transformers, the supplied three-phase voltage must be practically symmetrical. The no-load current can also be measured after switching on the transformer to operating voltage. In this case, to measure the no-load current value, stationary current transformers are used, in the secondary winding of which a control device is connected. You should not use detector system instruments for these measurements, since the shape of the no-load current curve is significantly different from a sinusoid, which leads to measurement errors. The magnitude of the no-load current of three-phase transformers is measured in all three phases and determined as the arithmetic mean of these values. The value of the no-load current of the transformer is not standardized.

  • Back
  • Forward
Rating
( 1 rating, average 5 out of 5 )
Did you like the article? Share with friends:
For any suggestions regarding the site: [email protected]
Для любых предложений по сайту: [email protected]