How to calculate the voltage drop along the cable length using the formula and table

In order to ensure the supply of voltage from the distribution device to the end consumer, power lines are used. They can be overhead or cable and have a considerable length.

Like all conductors, they have a resistance that depends on the length and the longer they are, the greater the voltage loss.


And the longer the line, the greater the voltage loss will be. Those. The voltage at the input and at the end of the line will be different.

In order for the equipment to operate without failures, these losses are normalized. Their total value should not exceed 9%.

The maximum voltage drop at the input is five percent, and to the most remote consumer no more than four percent. In a three-phase network with a three or four wire network, this figure should not exceed 10%.

Symptoms of low voltage in a consumer

If these indicators are not met, end users will not be able to provide the nominal parameters. When the voltage decreases, the following symptoms occur:

  • Lighting devices that use incandescent lamps begin to work (glow) at half incandescence;
  • When the electric motors are turned on, the starting force on the shaft decreases. As a result, the motor does not rotate, and as a result, the windings overheat and fail;
  • Some electrical appliances do not turn on. There is not enough voltage, and other devices may fail after switching on;
  • Installations that are sensitive to input voltage are unstable, and light sources that do not have an incandescent filament may also not turn on.

Electricity is transmitted via overhead or cable networks. Overhead ones are made of aluminum, while cable ones can be aluminum or copper.

In addition to active resistance, cables contain capacitive reactance. Therefore, the power loss depends on the cable length.

Reasons leading to a decrease in voltage

Voltage losses in power lines occur for the following reasons:

  • A current passes through the wire, which heats it, as a result, the active and capacitive resistance increases;
  • A three-phase cable with a symmetrical load has the same voltage values ​​on the cores, and the neutral wire current will tend to zero. This is true if the load is constant and purely active, which is impossible in real conditions;
  • In networks, in addition to the active load, there is a reactive load in the form of transformer windings, reactors, etc. and as a result, inductive power appears in them;
  • As a result, the resistance will consist of active, capacitive and inductive. It affects voltage losses in the network.

Current losses depend on the cable length. The longer it is, the greater the resistance, which means that the losses are greater. It follows that power losses in a cable depend on the length or length of the line.

Electricity losses in electrical networks: types, causes, calculation

Electricity losses in electrical networks are inevitable, so it is important that they do not exceed an economically justified level.

Exceeding technological consumption standards indicates problems that have arisen. To correct the situation, it is necessary to establish the causes of non-target costs and choose ways to reduce them.

The information collected in this article describes many aspects of this difficult task.

Types and structure of losses

Losses mean the difference between the electricity supplied to consumers and the energy actually received by them. To normalize losses and calculate their actual value, the following classification was adopted:

  • Technological factor. It directly depends on characteristic physical processes, and can change under the influence of the load component, semi-fixed costs, as well as climatic conditions.
  • Costs spent on operating auxiliary equipment and providing the necessary conditions for the work of technical personnel.
  • Commercial component. This category includes errors in metering devices, as well as other factors causing under-metering of electricity.

Below is an average graph of losses for a typical electric company.

Approximate loss structure

As can be seen from the graph, the highest costs are associated with transmission via overhead lines (power lines), this accounts for about 64% of the total losses. In second place is the corona effect (ionization of air near the overhead line wires and, as a consequence, the occurrence of discharge currents between them) – 17%.

Corona discharge on a power line insulator

Based on the presented graph, it can be stated that the largest percentage of non-targeted expenses falls on the technological factor.

Main causes of electricity losses

Having understood the structure, let's move on to the reasons that cause inappropriate expenditure in each of the categories listed above. Let's start with the components of the technological factor:

  1. Load losses occur in power lines, equipment and various elements of electrical networks. Such costs directly depend on the total load. This component includes:
  • Losses in power lines are directly related to current strength. That is why, when transmitting electricity over long distances, the principle of increasing it several times is used, which contributes to a proportional reduction in current and, accordingly, costs.
  • Consumption in transformers of a magnetic and electrical nature (1). As an example, below is a table that shows cost data for substation voltage transformers in 10 kV networks.

Losses in power transformers of substations

Non-target consumption in other elements is not included in this category due to the complexity of such calculations and the insignificant amount of costs. For this, the following component is provided.

  1. Category of semi-fixed expenses. It includes costs associated with the normal operation of electrical equipment, these include:
  • Idle operation of power plants.
  • Costs in equipment providing reactive load compensation.
  • Other types of costs in various devices, the characteristics of which do not depend on the load. Examples include power insulation, metering devices in 0.38 kV networks, measuring current transformers, surge limiters, etc.
  1. Climatic component. Inappropriate consumption of electricity may be associated with climatic conditions characteristic of the area where power lines pass. In networks of 6 kV and higher, the magnitude of the leakage current in the insulators depends on this. In main lines from 110 kV, a large share of the costs falls on corona discharges, the occurrence of which is facilitated by air humidity. In addition, in the cold season, our climate is characterized by such a phenomenon as icing on the wires of high-voltage lines, as well as ordinary power lines. Ice on power lines

Taking into account the last factor, the energy costs for melting ice should be taken into account.

Costs for supporting the operation of substations

This category includes the cost of electrical energy for the operation of auxiliary devices. Such equipment is necessary for the normal operation of the main units responsible for the conversion of electricity and its distribution. Costs are recorded using metering devices. Here is a list of the main consumers belonging to this category:

  • ventilation and cooling systems for transformer equipment;
  • heating and ventilation of the technological room, as well as internal lighting fixtures;
  • lighting of areas adjacent to substations;
  • battery charging equipment;
  • operational circuits and monitoring and control systems;
  • outdoor equipment heating systems, such as air circuit breaker control modules;
  • various types of compressor equipment;
  • auxiliary mechanisms;
  • equipment for repair work, communication equipment, as well as other devices.

Commercial component

These costs mean the balance between absolute (actual) and technical losses. Ideally, such a difference should tend to zero, but in practice this is not realistic.

This is primarily due to the characteristics of electricity meters and electricity meters installed at end consumers. It's about error.

There are a number of specific measures to reduce losses of this type.

https://www.youtube.com/watch?v=BSu1WKe6bEo

This component also includes errors in bills issued to consumers and theft of electricity. In the first case, a similar situation may arise for the following reasons:

  • the contract for the supply of electricity contains incomplete or incorrect information about the consumer;
  • incorrectly indicated tariff;
  • lack of control over meter data;
  • errors related to previously adjusted accounts, etc.

As for theft, this problem occurs in all countries. As a rule, such illegal actions are carried out by unscrupulous household consumers.

Note that sometimes incidents occur with enterprises, but such cases are quite rare, and therefore are not decisive.

It is typical that the peak of thefts occurs in the cold season, and in those regions where there are problems with heat supply.

There are three methods of theft (understating meter readings):

  1. Mechanical . This means appropriate intervention in the operation of the device. This can be slowing down the rotation of the disk by direct mechanical action, changing the position of the electric meter by tilting it by 45° (for the same purpose). Sometimes a more barbaric method is used, namely, the seals are broken and the mechanism is unbalanced. An experienced specialist will instantly detect mechanical interference.
  2. Electric . This can be an illegal connection to an overhead line by “throwing”, a method of investing a phase of the load current, as well as the use of special devices for its full or partial compensation. In addition, there are options with shunting the current circuit of the meter or switching phase and zero.
  3. Magnetic . With this method, a neodymium magnet is brought to the body of the induction meter.

The magnet can only affect some older models of electricity meters

Almost all modern metering devices cannot be “deceived” using the methods described above. Moreover, such attempts to interfere can be recorded by the device and stored in memory, which will lead to dire consequences.

The concept of loss standard

This term means the establishment of economically sound criteria for non-target expenditure for a certain period. When standardizing, all components are taken into account. Each of them is carefully analyzed separately.

As a result, calculations are made taking into account the actual (absolute) level of costs for the past period and an analysis of various opportunities that make it possible to realize the identified reserves to reduce losses.

That is, the standards are not static, but are regularly revised.

The absolute level of costs in this case means the balance between the transferred electricity and technical (relative) losses. Technological loss standards are determined by appropriate calculations.

Who pays for lost electricity?

It all depends on the defining criteria. If we are talking about technological factors and costs of supporting the operation of related equipment, then payment for losses is included in the tariffs for consumers.

The situation is completely different with the commercial component; if the established loss rate is exceeded, the entire economic load is considered an expense for the company that supplies electricity to consumers.

Ways to reduce losses in electrical networks

Costs can be reduced by optimizing the technical and commercial components. In the first case, the following measures should be taken:

  • Optimization of the circuit and operating mode of the electrical network.
  • Study of static stability and identification of powerful load nodes.
  • Reduction of total power due to the reactive component. As a result, the share of active power will increase, which will have a positive impact on the fight against losses.
  • Transformer load optimization.
  • Equipment modernization.
  • Various load balancing methods. For example, this can be done by introducing a multi-tariff payment system, in which the cost of kWh is increased during peak load hours. This will significantly reduce the consumption of electricity during certain periods of the day; as a result, the actual voltage will not “sag” below acceptable standards.

You can reduce your business costs by:

  • regular search for unauthorized connections;
  • creation or expansion of units exercising control;
  • checking readings;
  • automation of data collection and processing.

Methodology and example for calculating electricity losses

In practice, the following methods are used to determine losses:

  • carrying out operational calculations;
  • daily criterion;
  • calculation of average loads;
  • analysis of the greatest losses of transmitted power by day and hour;
  • access to generalized data.

Full information on each of the methods presented above can be found in regulatory documents.

https://www.youtube.com/watch?v=BSu1WKe6bEou0026t=131s

In conclusion, we give an example of calculating costs in a TM 630-6-0.4 power transformer. The calculation formula and its description are given below; it is suitable for most types of similar devices.

Calculation of losses in a power transformer

To understand the process, you should familiarize yourself with the main characteristics of TM 630-6-0.4.

Parameters TM 630/6/0.4

Now let's move on to the calculation.

Calculation results

List of used literature

  • Y. Zhelezko “Electricity losses. Reactive power. Power Quality: A Guide for Practical Calculations" 2009
  • Pospelov G.E. “Power and energy losses in electrical networks” 1981
  • Shvedov G.V., Sipacheva O.V.
    , Savchenko O.V. “Losses of electricity during its transport through electrical networks: calculation, analysis, regulation and reduction” 2013
  • Fursanov M.I.
    “Definition and analysis of electricity losses in electrical networks of power systems” 2005

Loss Value Calculation


To ensure the operability of the equipment, it is necessary to make a calculation. It is carried out at the time of design. The current level of development of computer technology allows calculations to be made using an online calculator, which allows you to quickly calculate cable power losses.

To calculate, just enter the required data. Set the current parameters - direct or alternating. The power line material is aluminum or copper. Indicate by what parameters the power loss is calculated - by cross-section or diameter of the wire, load current or resistance.

Additionally, indicate the network voltage and cable temperature (depending on operating conditions and installation method). These values ​​are inserted into the calculation table and calculated using an electronic calculator.

You can make a calculation based on mathematical formulas. In order to correctly understand and evaluate the processes occurring during the transmission of electrical energy, a vector form of representing characteristics is used.

And to minimize calculations, a three-phase network is represented as three single-phase networks. Network resistance is represented as a series connection of active and reactive resistance to the load resistance.

In this case, the formula for calculating power loss in a cable is significantly simplified. To obtain the necessary parameters, use the formula.

∆U= I*RL.

This formula shows the power loss of a cable as a function of the current and resistance distributed along the length of the cable.

However, this formula is valid if you know the current strength and resistance. Resistance can be calculated using the formula. For copper it will be equal to p=0.0175 Ohm*mm2/m, and for aluminum p=0.028 Ohm*mm2/m.

Knowing the value of resistivity, calculate the resistance, which will be determined by the formula

R=р*I/S, where р is resistivity, I is line length, S is cross-sectional area of ​​the wire.

In order to calculate voltage losses along the cable length, you need to substitute the obtained values ​​into the formula and perform calculations. These calculations can be made when installing electrical networks or security systems and video surveillance.

If power loss calculations are not made, this may lead to a decrease in the supply voltage to consumers. As a result, the cable will overheat, it may become very hot, and as a result, the insulation will be damaged.

Which may cause electric shock or short circuit to people. A decrease in line voltage can lead to failure of electronic equipment.

Therefore, when designing electrical wiring, it is important to calculate the voltage loss in the supply wires and the laid cable.

Cable loss calculation

During operation, the conductors heat up and generate heat. The higher the voltage and resistance of the cores, the greater the losses in the cable.

Losses can be calculated using the formula: ΔU=(Unom-U)∙100/ Unom, where: Unom is the rated voltage at the cable input, U is the voltage supplied to the load. Losses are indicated as a percentage of the rated voltage.

To avoid errors in calculations, it is customary to use Knorring tables based on the relationship between the power of the current load and the length of the power line.

Table 1 Voltage 220 V

ΔU, % Load moment for copper conductors, kW∙m, two-wire lines for voltage 220 V
With conductor cross section s, mm2, equal to
1,5 2,5 4 6 10 16
0,2 4 6 10 14 24 38
0,4 7 12 19 29 48 77
0,6 11 18 29 43 72 115
0,8 14 24 38 58 96 154
1 18 30 48 72 120 192
1,2 22 36 58 86 144 230
1,4 25 42 67 101 168 269
1,6 29 48 77 115 192 304
1,8 32 54 86 130 216 346
2 36 60 96 144 240 384
2,2 40 66 106 158 264 422
2,4 43 72 115 173 288 461
2,6 47 78 125 187 312 499
2,8 50 84 134 202 336 538
3 54 90 144 216 360 576
3,2 58 96 154 230 384 614
3,4 61 102 163 245 408 653
3,6 65 108 173 259 432 691
3,8 68 144 182 274 456 730
4 72 120 192 288 480 768
4,2 76 126 202 302 504 806
4,4 79 132 211 317 528 845
4,6 83 138 221 331 552 883
4,8 86 144 230 346 576 922
5 90 150 240 360 600 960

Table 2 Voltage 380/220 V for three-phase and four-phase lines. When there is a difference in loads in the lines, calculations are made according to Table 1.

ΔU, % Load moment for copper conductors, kW∙m, four-wire three-phase lines with zero for voltage 380/220 V or three-wire three-phase without zero for 380 V with conductor cross-section s, mm2 equal
1.5 2,5 4 6 10 16 25 35 50 70 95 120 150 185
0,2 22 36 58 86 144 230 360 504 720 1 008 1 368 1 728 2 160 2 664
0,4 43 72 115 173 288 461 720 1 008 1 440 2 016 2 736 3 456 4 320 5 328
0,6 65 108 173 259 432 691 1 080 1 512 2 160 3 024 4 104 5 184 6 480 7 992
0,8 86 144 230 346 576 922 1 440 2 016 2 880 4 032 5 472 6 912 8 640 10 656
1 108 180 288 432 720 1 152 1 800 2 520 3 600 5 040 6 840 8 640 10 800 13 320
1,2 130 216 346 518 864 1 382 2 160 3 024 4 320 6 048 8 208 10 368 12 960 15 984
1,4 151 252 403 605 1 008 1 613 2 520 3 528 5 040 7 056 9 576 12 096 15 120 18 648
1,6 173 288 462 691 1 152 1 843 2 880 4 032 5 760 8 064 10 944 13 824 17 280 21 312
1,8 194 324 518 778 1 296 2 074 3 240 4 536 6 480 9 072 12 312 15 552 19 440 23 976
2 216 360 576 864 1 440 2 304 3 600 5 040 7 200 10 080 13 680 17 280 21 600 26 640
2,2 238 396 636 950 1 584 2 534 3 960 5 544 7 920 11 088 15 048 19 008 23 760 29 304
2,4 259 432 691 1 037 1 728 2 765 4 320 6 048 8 640 12 096 16 416 20 736 25 920 31 968
2,6 281 478 749 1 121 1 872 2 995 4 780 6 552 9 360 13 104 17 784 22 464 28 100 34 632
2,8 302 504 806 1 210 2 016 3 226 5 040 7 056 10 080 14 112 19 152 24 192 30 200 37 296
3 324 540 864 1 296 2 160 3 456 5 400 7 560 10 800 15 120 20 520 25 920 32 400 39 960
3,2 346 576 922 1 386 2 304 3 686 5 760 8 064 11 520 16 128 21 888 27 648 34 560 42 624
3,4 367 612 979 1 469 2 448 3 917 6 120 8 568 12 240 17 136 23 256 29 376 36 720 45 280
3,6 389 648 1 037 1 555 2 592 4 147 6 480 9 072 12 960 18 144 24 624 31 104 38 880 47 952
3,8 410 684 1 094 1 642 2 736 4 378 6 840 9 576 13 680 19 152 25 992 32 832 41 040 50 616
4 432 720 1 152 1 728 2 880 4 608 7 200 10 080 14 400 20 160 27 360 34 560 43 200 53 280
4,2 454 756 1 210 1 814 3 024 4 838 7 560 10 584 15 120 21 168 28 728 36 288 45 360 55 944
4,4 475 792 1 267 1 901 3 168 5 069 7 920 11 088 15 840 22 176 30 096 38 016 47 520 58 608
4,6 497 828 1 325 1 987 3 321 5 299 8 280 11 592 16 560 23 184 31 464 39 744 49 680 61 272
4,8 518 864 1 382 2 074 3 454 5 530 8 640 12 096 17 280 24 192 32 832 41 472 51 840 63 936
5 540 900 1 440 2 160 3 600 5 760 9 000 12 600 18 000 25 200 34 200 43 200 54 000 66 600

Table 3 Voltage 12 W (copper conductor, line of two wires)

ΔU, % Load moment for copper conductors, kW∙m, two-wire lines for 12 V voltage
With conductor cross section s, mm2, equal to
1,5 2,5 4 6 10 16
1 0,05 0,09 0,14 0,22 0,36 0,58
2 0,1 0,18 0,29 0,43 0,72 1,15
3 0,16 0,27 0,43 0,65 1,08 1,73
4 0,22 0.36 0,58 0,86 1,44 2,3
5 0.27 0,45 0,72 1,08 1,8 2,88
6 0,32 0,54 0,86 1,3 2,16 3,46
7 0,38 0,63 1,0 1,51 2,52 4,03
8 0,44 0,72 1,16 1,72 2,88 4,6
9 0,49 0,81 1,3 1,94 3,24 5,18
10 0,54 0,9 1,44 2,16 3,6 5,76

Optimal operation of the power cable is possible with a loss of no more than 5%.
If the resulting figure is higher, it is necessary to replace the cable with a larger cross-sectional area of ​​the conductor. Otherwise, the system will not work, and the likelihood of a short circuit also increases. It is also not worth buying a power cable with a larger cross-section than necessary. This significantly increases the cost of operating networks. When choosing a cable, be guided by the indicators obtained during calculations.

Loss reduction methods

Power losses can be reduced by the following methods:

  • Increase the cross-section of conductors. As a result, resistance will decrease and losses will decrease;
  • Reduced power consumption. This setting cannot always be changed;
  • Changing the cable length.

Reducing power and changing line length is practically impossible. Therefore, if you increase the cross-section of the wire without calculation, then on a long line this will lead to unjustified costs.

This means that it is very important to make a calculation that will allow you to correctly calculate the power losses in the cable and select the optimal cross-section of the cores.

Rating
( 2 ratings, average 5 out of 5 )
Did you like the article? Share with friends:
For any suggestions regarding the site: [email protected]
Для любых предложений по сайту: [email protected]