What wire is needed to ground a private house?

Good day. When laying wiring in a private house, how to properly ground?

In order to leave your answer to a question, you must log in or go through a quick registration procedure Register!

In a modern private home there are many electrical appliances that need to be grounded to ensure their safe use.

The cross-section of the wire for grounding in a private house is selected depending on its operating conditions. The Electricity Supply Rules (PUE) state that any power-consuming device with a voltage of 220V must be connected to the electrical network with a cable of three wires. The third wire is the neutral ground wire or ground wire. With an existing 380V network, a four-wire cable must be used for power supply.

Properly performed grounding should be a closed loop. The grounding loop is connected to the PE bus using a copper wire. The cross-section of the wire for grounding in a private house, when using insulated wires of a single-phase network, must be at least 2.5 mm2. In this case, you need to know that the cross-section of the grounding wire is always smaller than the cross-section of the wires through which the current passes.

When using a non-insulated phase input into a house made of copper wire with a cross-section of 6 mm2, stranded copper wires of the same cross-section are used for grounding.

If the power distribution panel, when entering the building, is made correctly, it should contain phase wires and a “neutral”, and a PE grounding bus should be present. The grounding wires of electrical appliances are connected to it. The PE bus is connected to the ground loop of the entire building. The grounding loop includes the following elements: electric current consumers, a distribution panel, with a PE grounding bus, a grounding conductor and a grounding conductor.

Grounding conductors can be existing suitable elements; in their absence, artificial grounding conductors can be made. They can be used as steel reinforcement with a diameter of at least 16 mm or a steel angle with a side of 50 mm. These are vertical grounding conductors; they are driven into the ground. To obtain a closed loop, vertical grounding conductors must be linked with horizontal connections. To do this, use metal corners or wire. They are connected by welding or bolts. The connection must be continuous. The resulting circuit is connected to a grounding bus and a grounding conductor.

After creating a grounding loop, you need to measure its resistance and compare its value with the permissible standards of PUE and PTEEP.

Modern household appliances and equipment require grounding. Only in this case will manufacturers maintain their guarantees. Residents of apartments have to wait for the networks to be overhauled, while home owners can do everything themselves. How to make grounding in a private house, what is the procedure and connection diagrams - read about all this here.

Types of ground loops

In general, ground loops can be in the form of a triangle, rectangle, oval, line or arc. The best option for a private home is a triangle, but others are also quite suitable.

Grounding in a private house - types of grounding loops

Triangle

Grounding in a private house or country house is most often done with a contour in the form of an isosceles triangle. Why is that? Because with such a structure, in a minimum area we obtain a maximum area for current dissipation. The costs of installing a grounding loop are minimal, and the parameters correspond to the standards.

Most often, grounding in a private house is done with a triangle-shaped circuit

The minimum distance between the pins in the ground loop triangle is their length, the maximum is twice the length. For example, if you drive the pins to a depth of 2.5 meters, then the distance between them should be 2.5-5.0 m. In this case, when measuring the resistance of the ground loop, you will get normal values.

During work, it is not always possible to make the triangle strictly isosceles - stones come across in the right place or other difficult-to-pass areas of soil. In this case, you can move the pins.

Linear ground loop

In some cases, it is easier to make a ground loop in the form of a semicircle or a chain of pins lined up (if there is no free area of ​​suitable dimensions). In this case, the distance between the pins is also equal to or greater than the length of the electrodes themselves.

With a linear circuit, a larger number of vertical electrodes is necessary so that the dissipation area is sufficient

The disadvantage of this method is that to obtain the required parameters, a larger number of vertical electrodes is required. Since hammering them in is still a pleasure, if there is a meta, they try to make a triangular outline.

Grounding and its reliability: what cross-section should the conductor be?

In order to perform complete and reliable grounding and protect against electric shock, you should carefully approach the issue of choosing the cross-section of cable products.

To correctly select the cross-section of the grounding conductor, it is necessary to take into account the cross-section of each phase wire supplying the device: only in this case the conductor will not burn out, but will actually fulfill the task assigned to it, ensuring the protection of a person from electric shock.

When determining the cross-section of the wire for grounding, you should proceed from the following settings:

  • if the supply phase wire has a cross-section of up to 16 mm 2, the thickness of the grounding conductor should be similar;
  • in the presence of phase wires with a cross-section of 16÷35 mm 2, the cross-section of the grounding conductor is 16 mm 2;
  • if the cross-section of the phase wire exceeds 35 mm 2, the cross-section of the ground electrode should not be less than half the cross-section of the phase.

To illustrate this, I will give two specific examples:

  1. If the electric stove is connected with a cable whose core cross-section is 4 mm 2, a 4 mm 2 grounding should be used.
  2. If each of the wires of the power cable of the electrical cabinet has a cross-section of 50 mm 2, therefore, the grounding cross-section should be 25 mm 2 or more.

Ground loop materials

For the grounding of a private house to be effective, its resistance should not be more than 4 ohms. To do this, it is necessary to ensure good contact of the grounding conductors with the ground. The problem is that grounding resistance can only be measured with a special device. This procedure is carried out when putting the system into operation. If the parameters are worse, the act is not signed. Therefore, when doing the grounding of a private house or cottage with your own hands, try to strictly adhere to the technology.

Example of grounding for a private house

Pin parameters and materials

Grounding pins are usually made of ferrous metal. Most often, a rod with a cross-section of 16 mm or larger or a corner with parameters 50 * 50 * 5 mm (5 cm shelf, metal thickness - 5 mm) is used. Please note that reinforcement cannot be used - its surface is hardened, which changes the distribution of currents, and in addition, in the ground it quickly rusts and collapses. What is needed is a rod, not reinforcement.

Read also: Calculation of the power of a toroidal transformer by core

Possible electrode profiles

Another option for arid regions is thick-walled metal pipes. Their lower part is flattened into a cone, and holes are drilled in the lower third. To install them, holes of the required length are drilled, since they cannot be driven in. When soils dry out and grounding parameters deteriorate, a saline solution is poured into the pipes to restore the dissipative capacity of the soil.

The length of the grounding rods is 2.5-3 meters. This is sufficient for most regions. More specifically there are two requirements:

  • the grounding loop rod must extend into the ground below the freezing level by at least 60 cm (preferably 80-100 cm);
  • in arid regions, at least 1/3 of the ground electrode should be in wet soils, so you also need to focus on the level of groundwater - if it is low, longer rods may be needed.

The most commonly used steel angle and strip

Specific grounding parameters can be calculated, but the results of a geological study are required. If you have any, you can order a calculation from a specialized organization.

What to make metal connections from and how to connect them with pins

All pins of the circuit are connected to each other by metal bonding. It can be made from:

  • copper wire with a cross section of less than 10 mm 2;
  • aluminum wire with a cross-section of at least 16 mm 2
  • steel conductor with a cross section of at least 100 mm 2 (usually a strip of 25 * 5 mm).

Most often, the pins are connected to each other using a steel strip. It is welded to the corners or heads of the rod. It is very important that the quality of the weld is high - this determines whether your grounding will pass the test or not (whether it will meet the requirements - resistance less than 4 ohms).

Parameters that must be achieved when making a ground loop yourself

When using aluminum or copper wire, a large cross-section bolt is welded to the pins, and the wires are already attached to it. The wire can be screwed onto a bolt and pressed with a washer and nut, or the wire can be terminated with a connector of a suitable size. The main task is the same - to ensure good contact. Therefore, do not forget to strip the bolt and wire to bare metal (can be treated with sandpaper) and tighten well - for good contact.

Ground wire size

To ensure reliable protection against electric shock and the operation of protective switching devices, the grounding wire is selected depending on the phase cross-section. This is necessary so that in the event of an accident it can withstand high currents and not burn out. If this happens, the protection will not work, and dangerous potential will appear on the body of the electrical device.

The cross-section of the ground wire should be:

  • If a phase is used with a cross section of up to 16 sq. mm - the grounding conductor must be of a similar size.
  • If the cross-sectional area of ​​the phase is from 16 to 35 sq. mm, then at the “ground” it should be 16 square meters. mm.
  • When the phase cross-section is more than 35 sq. mm - the minimum cross-section of the ground wire must be at least half the cross-section of the phase wire.

Let's give two examples to answer the question of what cross-section the device grounding should have:

  1. You connect the electric stove with a cable with a core cross-section of 4 square meters. mm. This means that the cross-section of the protective wire should be the same.
  2. An input cable with 50 sq. conductors is connected to the electrical cabinet. mm. In this case, the grounding cross-section must be at least 25 square meters. mm. More is possible.

How to make grounding yourself

After all materials have been purchased, you can begin the actual manufacture of the ground loop. First, cut the metal into pieces. Their length should be about 20-30 cm longer than the calculated one - when driven in, the tops of the pins bend, so you have to cut them off.

Sharpen the clogged edges of the vertical electrodes - things will go faster

There is a way to reduce the resistance when driving electrodes - sharpen one end of the angle or pin at an angle of 30°. This angle is optimal when driving into the ground. The second point is to weld a metal pad to the upper edge of the electrode, from above. Firstly, it is easier to hit, and secondly, the metal is less deformed.

Work order

Regardless of the shape of the contour, it all starts with excavation work. It is necessary to dig a ditch. It is better to make it with beveled edges - this way it crumbles less. The order of work is as follows:

  • The area where the grounding loop will be placed is cleared and markings are applied.
  • According to the markings, they dig a trench 70-80 cm deep and about 50 cm wide. The depth is not accidental - if you lay the metal connection lower or higher, the metal will corrode faster.
  • The prepared pins are placed in the designated places and hammered until a section of about 20 cm remains above the surface.

The process of manufacturing a grounding loop - for grounding in a private house

Only the weld areas need to be painted.

Ground loop diagram with dimensions

Actually, that's all. We did the grounding in a private house with our own hands. All that remains is to connect it. To do this, you need to understand the grounding organization diagrams.

Inserting a ground loop into the house

The ground loop must somehow be connected to the ground bus. This can be done using a steel strip of 24 * 4 mm, copper wire with a cross-section of 10 mm2, and aluminum wire with a cross-section of 16 mm2.

If wires are used, it is better to look for them in insulation. Then a bolt is welded to the circuit, and a sleeve with a contact pad (round) is put on the end of the conductor. A nut is screwed onto the bolt, a washer is screwed onto it, then a wire, another washer is placed on top, and the whole thing is tightened with a nut (picture on the right).

How to bring “earth” into the house

When using a steel strip, there are two options - bring a tire or wire into the house. I really don’t want to pull a steel tire measuring 24*4 mm - it looks unaesthetic. If there is, you can use the same bolted connection to install a copper busbar. It needs a much smaller size, it looks better (photo on the left).

You can also make a transition from a metal bus to a copper wire (cross section 10 mm2). In this case, two bolts are welded to the tire at a distance of several centimeters from each other (5-10 cm). The copper wire is twisted around both bolts, pressing them with a washer and nut to the metal (tighten as best as possible). This method is the most economical and convenient. It doesn't require as much money as using only copper/aluminum wire, and it's easier to run it through the wall than a busbar (even a copper one).

How to choose the right cross-section of the grounding conductor

Example of a cable with a smaller PEN core cross-section

To connect the protection system, not only natural grounding conductors can be used, but also artificial ones. The selection rules in each case differ from each other and have their own technical features.

Networks with a power of more than 1 kW are equipped with artificial ones; in other cases, the operation of natural ones is permissible.

The artificial segment is made of galvanized alloys, steel and copper. The cross-section is selected in accordance with the Electrical Equipment Installation Rules in special tables.

MaterialSection profileDiameter(mm)/Cross-sectional area(mm.sq)
Copper
  • Round
  • Rectangular
  • Pipe
  • Multi-wire rope
  • 12 mm
  • 50 mm.sq.
  • 20 mm
  • 1.8 mm/35 mm.sq.
Cink Steel
  • Round for vertical
  • Round for horizontal
  • Rectangular
  • Pipe
  • 12 mm
  • 10 mm
  • 75 mm.sq.
  • 25 mm
Black steel
  • Round for vertical
  • Round for horizontal
  • Rectangular
  • Angular
  • Pipe
  • 16 mm
  • 10 mm
  • 100 mm.sq.
  • 100 mm.sq.
  • 32

One simple but important rule is that the conductor must have a cross-section that is equal to the cross-section of the phase wire, provided that the conductor is at least 16 mm2. In other cases, the cross section is calculated using the table given in the PUE.

Section of phase conductors, mm.sq.Smallest cross-section of protected conductors, mm.sq.
S>35S/2
35>S>1616
S<16S

In an ordinary apartment, which is equipped with all the necessary equipment, it is enough to install a protection system with a single-core wire with yellow-green insulation.

Grounding schemes: which one is better to make?

Currently, in the private sector, only two grounding connection schemes are used - TN-CS and TT. For the most part, a two-core (220 V) or four-core (380 V) cable (TN-C system) is suitable for the house. With such wiring, in addition to the phase (phase) wire, there is a protective conductor PEN, in which neutral and ground are combined. At the moment, this method does not provide adequate protection against electric shock, so it is recommended to replace the old two-wire wiring with a three-wire (220 V) or five-wire (380 V).

Read also: How to tighten the cylinder head without a torque wrench

Two schemes that are used if you need to make grounding in a private house

In order to obtain normal three- or five-wire wiring, it is necessary to separate this conductor into ground PE and neutral N (in this case, an individual ground loop is required). This is done in the entrance cabinet on the facade of the house or in the accounting and distribution cabinet inside the house, but always before the meter. Depending on the separation method, either a TN-CS or TT system is obtained.

Installation of a TN-CS grounding system in a private house

When using this circuit, it is very important to make a good individual ground loop. Please note that with the TN-CS system, protection against electric shock requires the installation of RCDs and breakers. Without them there is no talk of any protection.

Also, to ensure protection, it is necessary to connect all systems that are made of conductive materials - heating, water supply, foundation reinforcement frame, sewerage, gas pipeline (if they are made of metal pipes) to the earth bus with separate wires (inextricable). Therefore, the grounding bus must be taken “with a reserve”.

Scheme for converting the TN-C system to TN-C-S

To separate the PEN conductor and create grounding in a private house TN-CS, three buses are needed: on a metal base - this will be a PE (ground) bus, and on a dielectric base - this will be an N (neutral) bus, and a small splitter bus for four " seating places.

The metal “ground” bus must be attached to the metal body of the cabinet so that there is good electrical contact. To do this, at the fastening points, under the bolts, the paint is removed from the body to bare metal. The zero bus - on a dielectric base - is best mounted on a DIN rail. This installation method fulfills the basic requirement - after separation, the PE and N buses should not intersect anywhere (should not have contact).

Grounding in a private house - transition from the TN-C system to TN-C-S

Next we connect like this:

  • The PEN conductor coming from the line is connected to the bus splitter.
  • We connect the wire from the ground loop to the same bus.
  • From one socket with a copper wire with a cross-section of 10 mm 2 we place a jumper on the ground bus;
  • From the last free socket we place a jumper on the zero bus or neutral bus (also a 10 mm 2 copper wire).

Now that's it - grounding in a private house is done according to the TN-CS scheme. Next, to connect consumers, we take the phase from the input cable, zero from the N bus, and ground from the PE bus. We make sure that ground and zero do not intersect anywhere.

Grounding according to the TT system

Converting a TN-C circuit to TT is generally simple. There are two wires coming from the pole. The phase conductor is further used as a phase, and the protective PEN conductor is attached to the “zero” bus and is then considered zero. The conductor from the made circuit is directly supplied to the grounding bus.

Do-it-yourself grounding in a private house - TT diagram

The disadvantage of this system is that it provides protection only for equipment that requires the use of an “earth” wire. If there are also household appliances made using a two-wire circuit, they may be energized. Even if the housings are grounded with separate conductors, in case of problems, the voltage may remain at “zero” (the phase will be broken by the machine). Therefore, of these two schemes, TN-CS is preferred as it is more reliable.

Grounding is the intentional contact of any point in the electrical network or equipment with a ground loop. Grounding ensures lightning protection and safe use of electrical household appliances. When carrying out wiring repairs, inexperienced technicians often do not know what color the grounding wire in the electrical wiring should be. Information about the color of wires is not difficult to understand, but it is necessary to know it in order to carry out electrical installation work safely and efficiently.

Now about grounding, grounding conductor and grounding conductor of a private house

Re-grounding of the neutral conductor when air powering the house can be done on a support pole or near the house.

Grounding on an overhead power line support

When installing an input device on a concrete support from which the power supply to the house branches off, it is quite justified and recommended to re-ground it using natural grounding conductors. As a natural grounding conductor, you can use the underground part of the support itself or its lightning protection circuit (clause 1.7.109-110, PUE).

Important! Re-grounding on a reinforced concrete pole is possible only if the overhead power line is made of insulated, self-supporting SIP type wires. Since they are mechanically stronger than wires without insulation.

But still, if you want a more reliable, safe and independent grounding device for your home, it is better to make it using artificial grounding conductors.

Grounding a house with artificially made ground electrodes

House grounding is a grounding device, which consists of the following elements: a grounding conductor and a grounding conductor.

A grounding conductor is a conductor or several conductors connected to each other and having contact with the ground. A grounding conductor is connected to the grounding conductor, which is carefully brought out near the house and connected to the main grounding bus (GZSH). The cross-section of the grounding conductor must be no less than the cross-section of the PEN conductor.

Grounding electrodes can be made in different versions and be of different types.

  • By type, grounding electrodes can be divided into: Vertical; Row; Ground loop.
  • By type, grounding electrodes can be described as: Pin, Modular-pin, Loop and Foundation grounding electrodes.

Purpose

According to the standards of PUE and GOST (18714-81), residential and industrial premises must have a protective grounding system. The grounding device is subject to testing, after which a report on its condition is drawn up.

The principle of operation of the grounding system is most easily explained using an example when a phase wire is damaged and a current leak occurs. In most cases, electrical wiring in a residential building is protected in the form of a residual current device. However, the RCD is effective in the presence of differential current (not always or not immediately available). Such a current manifests itself only when the conductor is connected to a point with a different potential. Since the earth resistance is high, the protective shutdown device is triggered.

However, if, for the reasons stated above, the RCD does not give the desired effect or such a device is absent altogether, then the current is directed to unprotected taps. This is a dangerous situation because it could result in an electric shock to the person who touches the tap.

What cross-section, quality and type of grounding wire should you choose for your apartment or house?

No one is immune from accidental electric shocks due to equipment failure, voltage surges, or for some less common reasons. An effective and inexpensive way to protect yourself and your loved ones (workers and subordinates, if we are talking about work equipment) from electric shock is grounding. But first, let us briefly recall the physics of its action and purpose.

Marking

Ground wires are designated in two ways:

Ground color

Grounding is usually indicated by the color yellow-green. Pure yellow or light green wires are much less common. The cable may have a blue braid at the ends where it is fixed, which indicates grounding in conjunction with zero.

In a switchboard, the grounding is connected to the grounding bus, the housing and the metal door of the switchboard. In the junction box, the connection is routed to the ground wires from the lighting fixtures and the ground contacts of the outlets.

Note! The grounding conductor should not be connected to the residual current device.

The following shows the grounding symbol on electrical circuit diagrams.

  1. Standard grounding.
  2. Clean grounding.
  3. Protective grounding.
  4. Grounding to the electrical equipment housing.
  5. Grounding for DC current.

Neutral color

The neutral conductor is indicated in blue. In the distribution board it is connected to the neutral bus, marked with the letter N. All blue conductors are also connected there. The bus is connected to the input through an electric meter or directly, without installing a machine. In the distribution box, all blue wires (except for the wire from the switch) are not involved in switching. In sockets, the neutral conductors are connected to a contact, which is designated by the letter N (located on the back of the socket).

Read also: What pressure does cold welding hold?

Phase color

The color scheme for marking the phase wire is more varied compared to grounding and neutral. Use brown, black, red or any other colors except yellow, green and blue.

In the switchboard, the phase leaving the consumer is connected to the lower contact of the automatic switch or residual current device. Phase switching occurs in switches. After closing the contact, the voltage is directed to consumers. In phase sockets, the black conductor should be connected to the contact marked with the letter L.

Letters in markings

To indicate the types of wires, the following letter designations are used:

  1. A - the conductor core is made of aluminum. If A is not indicated in the marking, the core is made of copper.
  2. AA is a stranded conductor with an aluminum core and additional aluminum braiding.
  3. AC - there is an additional lead braid.
  4. B - the cable belongs to the moisture-protected category. The braid is made of two-layer steel.
  5. BN - cable braid is resistant to fire.
  6. B - the shell is made of polyvinyl chloride.
  7. G - the shell is not used.
  8. r - the cable is bare and waterproof.
  9. K - control cable with wire winding.
  10. R - a rubber shell is used.
  11. NP - non-flammable rubber casing.

Independent wire designation

Sometimes there are conductors painted in colors that are unusual for them. Such color schemes do not comply with the standards specified in the Electrical Installation Rules. To make the task of arranging the wiring easier, it is recommended to do your own color marking. For this purpose, colored electrical tape is suitable, which is used to mark the ends of the conductors in the switchboard. Heat-shrinkable tubing is also used for marking. All that remains is to write down in a notepad the meanings of the colors with which this or that wire is marked.

Criteria for selecting a grounding cable


Grounding Schemes
Before choosing a grounding conductor, you need to understand several important points.

Owners of private houses and country buildings built in 1998 and earlier are forced to carry out grounding themselves. Modern buildings are equipped with a ready-made system even during the construction process.

To choose the right grounding wire and its cross-section, you need to find out what system is installed in the house. According to the Electrical Installation Rules, 4 types can be used:

  • TN-S - in the AC system, additional grounding is carried out using a neutral and a separate wire.
  • TN-C is characterized by combining the zero and ground wires, the neutral is output separately. The most common method of protection, which was used in Europe several decades ago.
  • TT – equipping electrical equipment with direct protective grounding.
  • IT – work directly with the housings of household appliances through complete insulation of all conductive cables and the housing itself.

The grounding diagram used should always be marked. In Russia you can find two of them:

  • PE – grounding;
  • PEN – neutral and ground are combined in one cable.

The next important selection criterion is the type of grounding used. Depending on their purpose, they are divided into two types - portable and stationary. In domestic conditions, a stationary type is sufficient, which allows the operation of both single-core and three-core cables.

Many people who are poorly informed in these surveys have difficulty figuring out what color the ground wire is. According to the requirements of the PUE, the wire must be made in yellow-green insulation color.

After determining the type of cable and material of the system, you can proceed to the next main step - selecting a suitable cross-section.

Popular brands

When selecting a cable brand, you should proceed from its type: stationary or mobile use. The stationary version is used to protect buildings, electrical panels and equipment. Multicore stranded cables (PVG, BBG), as well as single-wire modifications (NYM), are suitable for such purposes. Fixed type cables use a green-yellow grounding conductor. If the grounding cable is colorless, the ground is directed to the core.

NYM cable

The NYM brand is used for transporting electricity in stationary conditions. The cable is designed for alternating voltage with a frequency of 50 Hz. It is allowed to connect electrical equipment of the first security class to the conductor.

  • copper core;
  • the presence of an intermediate shell;
  • the color complies with the standard of the Rules for the Operation of Electrical Installations (green-yellow insulation);
  • Convenient for electrical installation work.

VVG cable

Products of this type are equipped with copper conductors of the first and second stranding classes. The insulating layer is always polyvinyl chloride. Some cable models are produced as multi-core cables. Three-, four-, five-core cables have a neutral and grounding. The insulation of the core intended for grounding is made of green-yellow polyvinyl chloride plastic.

Cable PV-3

Products of this type include one core, which contains twisted copper wires. When painting the shell, different colors are used. For grounding, yellow and green-yellow colors are used.

Cable PV-6

The cable design contains a multi-wire conductor made of copper. The insulating layer is made of transparent polyvinyl chloride plastic. The material is highly resistant to mechanical stress. Thanks to the transparency of the plastic compound, it is easy to monitor the integrity of the product. There are no standards for the color of the PV-6 shell. In connection with this circumstance, it is recommended to independently mark the cable with the desired color before carrying out electrical installation work.

ESUY cable

This type of cable is used to protect networks from short circuits. ESUY is also often used in power systems with significant currents. The cable is temperature resistant, lightweight and highly flexible. There is no voltage rating for ESUY because it is not designed to carry current. When laying the cable, you should take care of its color designation yourself.

Checking the correct marking and wiring

Color schemes in electrical engineering help speed up the identification of wires. However, you should not completely rely on color designations, since a connection error is quite possible. Based on this, it is recommended to check whether the colors match the intended purpose of the wires.

If the wires are not color coded, you will need an indicator. With its help, the phase is found. Where the indicator lights up is the phase. In other cases we are talking about zero and grounding.

If the wire is two-wire, there will be no problems identifying the right wire. However, in the case of a three-core cable, you cannot do without a multimeter. It is fixed in phase, after which the other contact of the conductor is checked. When zero is detected, the device will show 220 volts. For grounding, the indicator will be less than 220.

Rating
( 2 ratings, average 4 out of 5 )
Did you like the article? Share with friends:
For any suggestions regarding the site: [email protected]
Для любых предложений по сайту: [email protected]