Cable VVG 5x4: diameter, weight and other characteristics

We'll tell you how to calculate the cable cross-section and power by diameter - our tables and formulas will help you carry out the calculations yourself. In order to understand which wire you will need in different situations, you should distinguish the diameter of the cable cross-section. The table of values ​​can tell amateur electricians how to choose the right cable depending on its purpose in the future - connecting powerful household appliances, large equipment, or carrying electrical wiring into the house.

To carry out the measurement procedure yourself, it will be easiest to use special instruments: for example, using a micrometer you can get the most accurate result, which cannot be achieved with a regular ruler, although it can be used for such purposes. It should be remembered that the use of improvised means requires great precision and knowledge of calculation formulas.

General information about cable and wire

When working with conductors, it is necessary to understand their designation. There are wires and cables that differ from each other in their internal structure and technical characteristics. However, many people often confuse these concepts.

A wire is a conductor that has in its design one wire or a group of wires woven together and a thin common insulating layer.

A cable is a core or a group of cores that has both its own insulation and a common insulating layer (sheath).

Each type of conductor will have its own methods for determining cross sections, which are almost similar.

Conductor materials

The amount of energy that a conductor transmits depends on a number of factors, the main one of which is the material of the current-carrying conductors.

    The following non-ferrous metals can be used as the core material of wires and cables:
  1. Aluminum. Cheap and lightweight conductors, which is their advantage. They are characterized by such negative qualities as low electrical conductivity, a tendency to mechanical damage, high transient electrical resistance of oxidized surfaces;
  2. Copper. The most popular conductors, which have a high cost compared to other options. However, they are characterized by low electrical and transition resistance at the contacts, fairly high elasticity and strength, and ease of soldering and welding;
  3. Aluminum copper. Cable products with aluminum cores coated with copper. They are characterized by slightly lower electrical conductivity than their copper counterparts. They are also characterized by lightness, average resistance and relative cheapness.

Cable Diameter Guide

The outer diameter of the cable depends on the number and cross-section of the cores, on the presence, material and quantity of insulating, armoring and protective sheaths. Knowing the diameter is necessary to select cable-supporting structures, to determine containers and vehicles for transporting cable products.

The tables below indicate the nominal outer diameter of cables of different brands with different numbers and cross-sections of cores.

Outer diameter of cables with plastic insulation of brands VVG, AVVG, VBBShV and AVBBShV

Number of cores and cross-section (mm²) External diameter (mm)
VVG, AVVG VBBbShv, AVBbShv
3 x 35 23 27,6
3 x 50 27,1 31,3
3 x 70 28,7 32,9
3 x 95 32,1 36,8
3 x 120 36 40,2
3 x 150 39,2 43,5
3 x 185 42,7 47,3
3 x 240 48,9 53,2
3 x 35 + 1 x 16 28,4 28,2
3 x 50 + 1 x 25 29,2 30,8
3 x 95 + 1 x 50 37,4 39,2
3 x 120 + 1 x 70 38,9 44,1
3 x 150 + 1 x 70 44,6 47,6
3 x 185 + 1 x 50 53,6
3 x 185 + 1 x 70 50,2
4x 35 28,1 32,6
4x 50 32,4 35,6
4x 70 33,2 39
4x 95 37,1 43,3
4 x 120 41,2 47,4
4 x 150 43,9 50,2
4 x 185 49,4 54,4

Outer diameter of cables ASB, ASBl, ASB2L

Number and cross-section of cores

(mm2)

External diameter

(mm)

3x25 cooler 39,5
3x35 cooler 38,3
3x50 cool 40,2
3x70 cooler 42,9
3x70 44,4
3x95 cooler 45,9
3x95 47,5
3x120 coolant 48,3
3x120 50,3
3x150 coolant 50,7
3x150 52,9
3x185 coolant 53,6
3x185 56,3
3x240 coolant 57,8
3x240 62

NYM cable outer diameter

Number and cross-section of cores (mm2) External diameter (mm)
2×1,5 8,5
2×2,5 9,7
2×4 11,5
3×1,5 9,0
3×2,5 10,2
3×4 12,0
4×1,5 9,6
4×2,5 11,2
4×4 13,5
5×1,5 10,3
5×2,5 12,0

Outer diameter of cable KG

Section Diameter (mm)
1x16 12,3
1x25 15,3
1x35 16,5
1x50 19,0
1x70 21,8
2x1.5 11,2
2x2.5 12,7
3x1.5 11,8
3x2.5 13,4
3x1.5+1.5 12,7
3x2.5+1.5 15,5
3x4+2.5 16,8
3x6+4 18,5
3x10+6 22,7
3x16+6 24,5
3x25+10 29,9
3x35+10 34,7
3x50+16 41,3
3x70+25 45,2
3х95+35 51,0

Outer diameter of cables PVS, ShVVP

Number and cross-section of cores (mm2) PVS SHVVP
Diameter (mm) Diameter (mm)
2x0.5 3.1x5.1
2x0.75 6,2 3.3x5.4
2x1.5 7,8
2x2.5 9,1
3x0.75 6,6
3x1.5 8,4
3x2.5 9,6
4x1.5 9,1

Outer diameter of cables APV, PV-1, PV-3

Quantity and

core cross-section

(mm2)

Automatic reclosing PV-1 PV-3
Diameter (mm) Diameter (mm) Diameter (mm)
1,5 3 3,4
2,5 3,4 3,4 4,2
4 3,9 3,9 4,8
6 4,4 4,4 6,3
10 5,6 5,6 7,8
16 7,1 7,1 8,8
25 8,8 8,8 11
35 10 10 12,5
50 11,7 11,7 14,5
70 13,5 13,5 15,4
95 15,8 15,8 18,2
120 17

The tables provide reference information, which may differ from actual information.
intell-electro.ru

How and with what to measure the diameter of a wire (wire)

To measure the diameter of the wire, a caliper or micrometer of any type (mechanical or electronic) is suitable. It’s easier to work with electronic ones, but not everyone has them. You need to measure the core itself without insulation, so first move it aside or remove a small piece. This can be done if the seller allows it. If not, buy a small piece to test and take measurements on it.

On a conductor stripped of insulation, measure the diameter, after which you can determine the actual cross-section of the wire from the found dimensions. Which measuring device is better in this case? If we talk about mechanical models, then a micrometer. Its measurement accuracy is higher. If we talk about electronic options, then for our purposes they both give quite reliable results.

If you don't have a caliper or micrometer, take a screwdriver and a ruler with you. You'll have to strip a fairly decent piece of conductor, so you'll hardly be able to do without buying a test sample this time. So, remove the insulation from a 5-10 cm piece of wire.

Wind the wire around the cylindrical part of the screwdriver. Lay the coils close to each other, without a gap. All turns must be complete, that is, the “tails” of the wire must stick out in one direction - up or down, for example.

The number of turns is not important - about 10. You can have more or less, it’s just easier to divide by 10. Count the turns, then apply the resulting winding to the ruler, aligning the beginning of the first turn with the zero mark (as in the photo). Measure the length of the section occupied by the wire, then divide it by the number of turns. You get the diameter of the wire. It's that simple.

For example, let's calculate the size of the wire shown in the photo above. The number of turns in this case is 11, they occupy 7.5 mm. Divide 7.5 by 11, we get 0.68 mm. This will be the diameter of this wire. Next, you can look for the cross section of this conductor.

Methods for measuring conductor diameter

When selecting an electrical cable or wire to check the cross-section of the core, it is necessary to measure its diameter. There are several ways to do this. You can use measuring instruments such as calipers or micrometers. They measure the size of the exposed part of the conductor.

The device is simply attached to the core, clamped between the jaws, and the result is displayed on the scale. For private use, the measurements are quite accurate, with a small error. Especially if the devices are electronic.

For the second method, you only need a ruler and some kind of even rod. But in this case, you still have to do calculations, albeit very simple ones. More on this method later.

Ruler+rod

If there are no measuring instruments on the farm, you can get by with a regular ruler and any rod of the same diameter. This method has a high error, but if you try it will be quite accurate. Take a piece of wire about 10-20 cm long and remove the insulation.

We wind the bare copper or aluminum wire onto a rod of the same diameter (any screwdriver, pencil, pen, etc. will do). We lay the coils carefully, close to one another. The number of turns is 5-10-15. We count the number of full turns, take a ruler and measure the distance that the wound wire occupies on the rod. Then divide this distance by the number of turns. As a result, we obtain the diameter of the conductor.

For example, we wound 10 turns (it’s easier to count), they took up 3.8 cm (or 38 mm) on the rod. Next, we divide the distance by the number of turns, 38/10 = 3.8 mm, we get that the diameter of the wound wire is 3.8 mm.

As you can see, there is an error here. Firstly, you can lay the wire loosely. Secondly, it is not enough to take accurate measurements. But if you do everything carefully, the discrepancies with the actual sizes will not be so large.

Application of measuring instruments

To determine the diameter of the cores of wires and cables, various measuring instruments are widely used, showing the most accurate results. Basically, the use of micrometers and calipers is practiced for these purposes. Despite their high efficiency, a significant drawback of these devices is their high cost, which is of great importance if the tool is planned to be used only 1-2 times.

As a rule, professional electricians who are constantly engaged in electrical installation work use special devices. With the right approach, it becomes possible to measure the diameter of wire cores even on working lines.

External diameters and weight of cables

Power cables with paper insulation are manufactured in accordance with the requirements of GOST 18410-73 and GOST 18409-73, with plastic insulation - in accordance with the requirements of GOST 16442-80. The structural elements included in the cable, in accordance with the specified GOSTs, have certain limited tolerances from the nominal geometric dimensions. In this regard, the external diameters of the cables and their mass may vary within insignificant limits from the calculated ones. When designing and drawing up work projects in installation organizations, it is necessary to use the calculated outer diameters for each cable brand, depending on its design and core cross-section. For transportation and loading and unloading operations, it is necessary to take into account not only the weight of the cable, but also the weight of the cable drum. In table The calculated outer diameter and weight of cables with paper insulation for voltages of 1 and 10 kV and cables with plastic insulation for voltages of 1 kV are indicated.

External diameter, weight of three-core cables with copper conductors in a lead sheath of the SGU, SBGU, SBU and SBLU brands for a voltage of 1 kV according to GOST 18410-73

Number of cable cores x cross-section, mm2 External diameter, mm Estimated weight, kg/km
SSU SBSU SBU SBLU SSU SBSU SBU SBLU
3 x 35 20,2 25,3 29,7 30,7 2212 2440 2699 2780
3 x 35* 19,3 24,4 28,8 29,8 2127 2349 2599 2679
3 x 50 22,8 27,9 32,3 33,3 2806 3050 3334 3420
3 x 50* 20.3 25.7 30.1 31.1 2376 2727 2953 3033
3 x 70 24,8 30,1 34,5 35,5 3360 3711 3971 4211
3 x 95 28,1 33,3 37,7 38,7 4350 4711 4996 5094
3 x 120 31,7 36,8 41,2 42,2 5462 5788 6100 6206
3 x 150 36,9 41,8 46,2 47,2 7166 7366 7774 7895
3 x 185 41 45,6 50 57 8863 8814 9286 9412
3 x 240 45,8 50,6 55 58 10076 11499 11499 11641

* Solid wires

External diameter, weight of four-core cables with copper conductors in a lead sheath of the SGU, SBGU, SBU and SBLU brands for a voltage of 1 kV according to GOST 18410-73

Number of cores

x section, mm2

External diameter, mm Estimated weight, kg/ km
SSU SBSU SBU SBLU SSU SBSU SBU SBLU
3 x 35 + 1 x 16 22,1 27,2 31,6 32,6 2520 2761 3037 3123
3 x 35 + 1 x 16* 20,7 25,8 30,2 31,2 2395 2627 2889 2973
3 x 50 + 1 x 25 24,6 29,7 34,1 35,1 3218 3505 3804 3899
3 x 50 + 1 x 25* 22.8 27.9 32,3 33.3 3006 3255 3538 3625
3 x 70 + 1 x 25 28,6 33,8 38,2 39,2 4211 4545 4883 4985
3 x 95 + 1 x 35 30 35,2 39,6 42,4 4886 5244 5544 5647
3 x 120 + 1 x 35 33,4 38,5 42,9 46,6 5924 6262 6587 6698
3 x 120 + 1 x 70 35,4 42,5 44,9 47,9 6196 7016 7192 7291
3 x 150 + 1 x 50 36,6 43,6 46 50,1 7209 7501 7850 7969
3 x 185 + 1 x 50 43,9 48,5 52 53,9 9649 9721 10090 10225

External diameter, weight of four-core power cables with copper conductors in a lead sheath of the SGU, SBGU, SBU and SBLU brands for a voltage of 1 kV according to GOST 18410-73

Number of cores x cross-section, mm2 External diameter, mm Estimated weight, kg/ km
SSU SBSU SBU SBLU SSU SBSU SBU SBLU
4 x 35* 22,1 27,2 31,6 32,6 2659 2899 3174 3262
4x 35 24 29.1 33.5 34,5 2900 3152 3447 3568
4 x 50* 24,9 30 34,4 35,4 3474 3731 4033 4126
4x 50 28,6 33,8 38,2 39,2 3906 4243 4578 4680
4x 70 30,7 35,6 40 41 4937 5116 5468 5580
4x 95 34,2 39,1 43,5 44,5 6262 6450 6834 6951
4 x 120 38,7 43,6 48 49 7752 7954 8379 8504

* Solid wires

External diameter, weight of three-core cables with aluminum conductors in a lead sheath, brands ASGU, ASBGU, ASBU, ASKLU for voltage 10 kV according to GOST 18410-73

Number of cores X x section, mm2 External diameter, mm Estimated weight, kg/km
ASSU ASBSU ASBU ASCLU ASSU ASBSU ASBU ASCLU
3 x 35* 28,8 34 38,4 47,2 2578 2926 3216 6256
3 x 50* 30,7 35,9 40,3 49,1 2851 3216 3521 6667
3 x 70* 33,6 38,7 43,1 52 3349 3688 4014 7524
3 x 95* 36,6 41,8 46,2 55,2 4044 4337 4680 8486
3 x 120* 39,4 44,4 48,8 57,8 4596 4868 5259 9291
3 x 150 44,6 49,2 53,6 63 5929 5900 6373 11209
3 x 150* 41,8 46,7 51,1 60,2 5161 5402 5791 10104
3 x 185 47,9 52,5 56,9 66,3 6773 7673 7239 12373
3 x 185* 44,8 49,7 54,1 63,2 5882 6117 6529 11087
3 x 240 52,8 58,6 63 75,2 8022 8591 9151 16768
3 x 240* 49 55,8 58,1 67,4 6942 7356 7562 12534

* Solid wires

External diameter, weight of three-core cables with aluminum cores in an aluminum sheath of brands AAShvU, AAShpsU, AABlGU, AABlU, AAB2luU for voltage 10 kV according to GOST 18410-73

Number of cores External diameter, mm Estimated weight, kg/km
x section, mm2 AAShvU AAShpsU AABLGU ААБЛУ ААБ2лУ AASHvU AAShpsU AABLGU AABlU AAB2luU
3 x 35* 33,8 36 40,4 1518 1441 2096 2429 2464
3 x 50* 36,5 38,3 42,7 1792 1699 2377 2729 2766
3 x 70* 38,8 40,6 45 2077 1979 2698 3070 3110
3 x 70 40,8 42,6 47 2221 2117 2873 3262 3304
3 x 95* 41,7 43,3 47,9 2462 2356 3128 3526 3567
3 x 95 42,9 45,7 50,1 2642 2530 3342 3758 3803
3 x 120* 44,1 45,9 50,3 2810 2698 3513 3930 3976
3 x 120 48 49,4 53,8 3166 3031 3882 4329 4378
3 x 150* 47,4 48,8 53,2 3308 3176 4016 4458 4506
3 x 150 50,9 52,3 56,7 3631 3188 4390 4862 4916
3 x 185* 50,4 51,8 56,2 3805 3664 4557 5026 5976
3 x 185 53,9 55,8 59,7 4114 3963 4917 5415 5470
3 x 240* 54,2 55,6 60 4473 4321 5280 5780 5836
3 x 240 59,3 61,5 65,9 4988 4807 6467 7048 7079

External diameter, weight of three-core cables with paper insulation impregnated with a non-drip compound, brands TsSBU, TsASBU, TsAASHvU, TsAABLU for voltage 1 kV according to GOST 18409-73

Number of cores x cross-section, mm2 External diameter, mm Estimated weight, kg/: km
CSBU TsASBU CAASHvU TsAABLU CSBU TsASBU CAASHvU TsAABLU
3 x 35* 41,8 42 37,3 43,3 4564 3830 1755 2792
3 x 35 44,4 4954
3 x 50* 45,3 45,5 39,6 46,6 5448 4431 2010 3173
3 x 50 47 5692
3 x 70* 47,8 41,9 48,6 5001 2332 3552
3 x 70 52,9 49,9 44 51 6731 5291 2471 3745
3 x 95* 50,5 44,9 51,9 5547 2753 4051
3 x 95 52,9 52,9 47,7 54,3 7808 5890 2973 4292
3 x 120* 52,9 47,7 54,3 6066 3149 4469
3 x 120 56,4 56,4 51,2 57,8 9108 6710 3441 4846
3 x 150* 55,8 50,6 57,2 6849 3621 5014
3 x 150 59,2 59,2 54 60,6 11521 7350 3406 5361
3 x 185* 58,3 53,1 59,7 7471 4070 5523
3 x 185 63,5 63,5 67,5 64,9 12547 8899 4481 5658

* Solid wires

External diameter, weight of cables with plastic insulation of brands VVG, AVVG, VBbShv and AVBbShv for voltage 1 kV according to GOST 16442-80

Number of cores x cross-section, mm2 External diameter, mm Estimated weight, kg/km
VVG, AVVG VBBbShv, AVBbShv VVG A B C D VBBShv AVBbShv
3 x 35 23 27,6 1221 562 1688 1024
3 x 50 27,1 31,3 1720 780 2233 1294
3 x 70 28,7 32,9 2379 1054 2909 1584
3 x 95 32,1 36,8 3146 1348 3771 1973
3 x 120 36 40,2 3923 1545 4585 2314
3 x 150 39,2 43,5 4832 1867 5553 2715
3 x 185 42,7 47,3 5885 2384 6712 3211
3 x 240 48,9 53,2 7604 3062 8501 3959
3 x 35 + 1 x 16 28,4 28,2 1429 668 1919 1159
3 x 50 + 1 x 25 29,2 30,8 2005 907 2570 1472
3 x 70 + 1 x 35 33,2 35,6 2660 1176 3248 1764
Number of cores x cross-section, mm2 External diameter, mm Estimated weight, kg/km
VVG, AVVG VBBbShv, AVBbShv VVG A B C D VBBShv AVBbShv
3 x 95 + 1 x 50 37,4 39,2 3551 1534 4214 2196
3 x 120 + 1 x 70 38,9 44,1 4299 1809 5025 2535
3 x 150 + 1 x 70 44,6 47,6 5364 2112 6205 3058
3 x 185 + 1 x 50 53,6 7324 3509
3 x 185 + 1 x 70 50,2 5457 2642
4x 35 28,1 32,6 1615 737 2110 1231
4x 50 32,4 35,6 2247 995 2817 1564
4x 70 33,2 39 3106 1340 3661 1895
4x 95 37,1 43,3 4118 1721 4771 2374
4 x 120 41,2 47,4 5139 2112 5832 2804
4 x 150 43,9 50,2 6341 2556 7094 3309
4 x 185 49,4 54,4 7773 3105 8596 3928

External diameter, weight of cables with plastic insulation grades APsVG and APsBBShV for voltage 1 kV according to GOST 16442-80

Number of cores x cross-section, mm2 External diameter, mm Estimated weight, kg/km
APsVG APsBBShv APsVG APsBBShv
3 x 35 + 1 x 16 28,4 28,2 632 1122
3 x 50 + 1 x 25 29,2 30,8 856 1421
3 x 70 + 1 x 35 33,2 35,6 1102 1620
3 x 95 + 1 x 50 37,4 39,2 1443 2106
3 x 120 + 1 x 70 38,9 44,1 1708 2434
3 x 150 + 1 x 70 44,6 47,6 2090 2931
3 x 185 + 1 x 50 50,6 53,6 2503 3369

Outer diameters, mm, of three-core 660V cables with rubber insulation for fixed installation

Core cross-section, mm JWG SRB VRG, NRG Core cross-section, mm JWG SRB VRG, NRG Core cross-section, mm JWG SRB VRG, NRG
1 9 17 11 10 18 26 20 70 34 45 39.
1,5 10 18 12 16 20 28 22 95 40 50 44
2,5 11 18 13 25 24 34 27 120 43 54 47
4 12 19 14 35 26 37 29 150 47 58 52
6 13 20 15 50 31 41 34 185 52 63 57

About choosing a cable brand for home wiring

Making apartment electrical wiring from aluminum wires at first glance seems cheaper, but operating costs due to low reliability of contacts over time will be many times higher than the costs of electrical wiring made from copper.

It is recommended to make wiring exclusively from copper wires! Aluminum wires are indispensable when laying overhead electrical wiring, as they are light and cheap and, when properly connected, serve reliably for a long time.

Which wire is better to use when installing electrical wiring, single-core or stranded? From the point of view of the ability to conduct current per unit of cross-section and installation, single-core is better. So for home wiring you only need to use solid wire.

Stranded allows multiple bends, and the thinner the conductors in it, the more flexible and durable it is. Therefore, stranded wire is used to connect non-stationary electrical appliances to the electrical network, such as an electric hair dryer, an electric razor, an electric iron and all the others.

After deciding on the cross-section of the wire, the question arises about the brand of cable for electrical wiring. The choice here is not great and is represented by only a few brands of cables: PUNP, VVGng and NYM.

PUNP cable since 1990, in accordance with the decision of Glavgosenergonadzor “On the ban on the use of wires such as APVN, PPBN, PEN, PUNP, etc., produced according to TU 16-505. 610-74 instead of APV, APPV, PV and PPV wires according to GOST 6323-79*" is prohibited for use.

Cable VVG and VVGng - copper wires in double polyvinyl chloride insulation, flat shape. Designed for operation at ambient temperatures from −50°С to +50°С, for wiring inside buildings, outdoors, in the ground when laid in tubes. Service life up to 30 years.

The letters “ng” in the brand designation indicate the non-flammability of the wire insulation. Two-, three- and four-core wires are available with core cross-sections from 1.5 to 35.0 mm2. If in the cable designation there is a letter A (AVVG) before VVG, then the conductors in the wire are aluminum.

The NYM cable (its Russian analogue is the VVG cable) with round copper cores with non-flammable insulation, complies with the German standard VDE 0250. Technical characteristics and scope of application are almost the same as the VVG cable. Two-, three- and four-core wires are available with core cross-sections from 1.5 to 4.0 mm2.

As you can see, the choice for laying electrical wiring is not large and is determined depending on what shape the cable is more suitable for installation, round or flat. A round-shaped cable is more convenient to lay through walls, especially if the connection is made from the street into the room. You will need to drill a hole slightly larger than the diameter of the cable, and with a larger wall thickness this becomes relevant. For internal wiring, it is more convenient to use a VVG flat cable.

Conditions for installation and operation of the VVG power cable

Operation of VVG cable at ambient temperatures from -50°С to +50°С. Recommended for installation outdoors, in dry and damp industrial areas. The VVG cable, which has a filling between the cores, made in accordance with GOST, can be laid in the ground under conditions of low corrosive activity of the soil and the absence of significant mechanical loads. Can be laid without preheating at a temperature not lower than minus 15°C. The minimum bending radius during installation must be at least 7.5 times the outer diameter of the cable. Does not propagate combustion when laid alone. The service life of the VVG cable is 30 years.

Dependence of current, power and core cross-section

It is not enough to measure and calculate the cross-sectional area of ​​the cable based on the diameter of the core. Before installing wiring or other types of electrical networks, it is also necessary to know the capacity of the cable products.

    When choosing a cable, you must be guided by several criteria:
  • the strength of the electric current that the cable will pass;
  • consumer power;
  • current load exerted on the cable.

Power

The most important parameter during electrical installation work (in particular, cable laying) is throughput. The maximum power of electricity transmitted through it depends on the cross-section of the conductor. Therefore, it is extremely important to know the total power of the energy consumption sources that will be connected to the wire.

Typically, manufacturers of household appliances, appliances and other electrical products indicate on the label and in the documentation accompanying them the maximum and average power consumption.

For example, a washing machine can consume electricity ranging from tens of W/h during rinsing mode to 2.7 kW/h when heating water.

Accordingly, a wire with a cross-section that is sufficient to transmit electricity of maximum power must be connected to it. If two or more consumers are connected to the cable, then the total power is determined by adding the limit values ​​of each of them.

The average power of all electrical appliances and lighting devices in an apartment rarely exceeds 7500 W for a single-phase network. Accordingly, the cable cross-sections in the electrical wiring must be selected to this value.

It is recommended to round the cross-section towards higher power due to a possible increase in power consumption in the future. Typically, the next largest cross-sectional area from the calculated value is taken. So, for a total power of 7.5 kW, it is necessary to use a copper cable with a core cross-section of 4 mm2, which is capable of transmitting about 8.3 kW. The cross-section of the conductor with an aluminum core in this case must be at least 6 mm2, passing a current power of 7.9 kW.

In individual residential buildings, a three-phase power supply system of 380 V is often used. However, most equipment is not designed for such electrical voltage. A voltage of 220 V is created by connecting them to the network through a neutral cable with an even distribution of the current load across all phases.

Electric current

Often the power of electrical equipment and equipment may not be known to the owner due to the absence of this characteristic in the documentation or completely lost documents and labels. There is only one way out in such a situation - to calculate using the formula yourself.

Power is determined by the formula:

P = U*I

    Where:
  • P – power, measured in watts (W);
  • I – electric current strength, measured in amperes (A);
  • U is the applied electrical voltage, measured in volts (V).
    When the strength of the electric current is unknown, it can be measured using instrumentation:
  • ammeter;
  • multimeter;
  • current clamps.

After determining the power consumption and electric current, you can use the table below to find out the required cable cross-section.

Load

Calculation of the cross-section of cable products based on current load must be carried out to further protect them from overheating. When too much electric current passes through conductors for their cross-section, destruction and melting of the insulating layer can occur.

The maximum permissible long-term current load is the quantitative value of the electric current that can pass the cable for a long time without overheating. To determine this indicator, it is initially necessary to sum up the powers of all energy consumers.

After this, calculate the current load using the formulas:

single-phase network: I = P∑*Ki/U

three-phase network: I = P∑*Ki/(√3*U)

    Where:
  • P∑ – total power of energy consumers;
  • Ki – coefficient equal to 0.75;
  • U – electrical voltage in the network.

Main technical characteristics of cable VVG 5x4

We presented all the cable characteristics necessary for ordering and calculation in the form of a table.

Characteristic nameUnit change Meaning
GOSTGOST 31996-2012
Core class according to GOST 22483-20121
OKP code35 2122; 35 3371
Fire hazard classO1.8.2.5.4
Operating temperature range°C-50 to 50
Minimum installation temperature°C-15
Duration of operationyears30
Mains voltageINup to 1000
AC frequency in the networkHz50 Hz
Allowable tensile forceN600
Maximum permissible core heating temperature during short circuit°C160
Short circuit duration, no moreWith5
Estimated mass (weight) of the cable, 0.66 kVkg/km349
Estimated mass (weight) of one meter of cable, 0.66 kVkg/m349/1000
Estimated mass (weight) of cable, 1 kVkg/km400
Estimated mass (weight) of one meter of cable, 1 kVkg/m400/1000
Allowable bending radiusmm152
Permissible current load when laying in airA36
Permissible current load when laying in the groundA47
Permissible one-second short circuit currentA0.43
Volume of combustible massl/km202
Core insulation resistanceMOhm/km10
Core insulation thickness, 1 kVmm1
Core insulation thickness, 0.66 kVmm0.7
Mass of non-ferrous metalg/m178
Maximum power when installed in air, 220 VkW10.56
Maximum power when installed in the ground, 220 VkW13.79
Maximum power when installed in air, 380 VkW23.69
Maximum power when installed in the ground, 380 VkW30.93
Core heating temperature based on non-ignition conditions°C350
Long-term permissible core heating temperature°C70
Permissible temperature in overload mode°C90
Electrical resistance of the conductorOhm/km4.61

Expert opinion

Chief Editor of LinijaOpory

Alexander Novikov is the main author and inspirer of our site. Author of diagrams and drawings.

Before making calculations, we recommend that you additionally request cable characteristics from the manufacturer!

Stranded wire

The PVS cable for connecting power tools and electrical appliances is made flexible, since all the cores are stranded. Measuring the diameter of the harness at the same time will give an incorrect result, since there are air gaps inside. The correct calculation principle is the same as for cable.

The core should be fluffed up, count how many wires are in it, and then measure the diameter of one of them. Knowing their total number in the vein, you can calculate the total cross-section using the previous formula. It’s best to take measurements using a micrometer. It is more convenient to use, since the caliper easily presses through thin wires.

How to calculate the cross-section of a stranded wire

Stranded wire, or as it is also called stranded or flexible, is a single-core wire twisted together. To calculate the cross-section of a stranded wire, you must first calculate the cross-section of one wire, and then multiply the resulting result by their number.

Let's look at an example. There is a multi-core flexible wire, in which there are 15 cores with a diameter of 0.5 mm. The cross-section of one core is 0.5 mm × 0.5 mm × 0.785 = 0.19625 mm2, after rounding we get 0.2 mm2. Since we have 15 wires in the wire, to determine the cable cross-section we need to multiply these numbers. 0.2 mm2×15=3 mm2. It remains to determine from the table that such a stranded wire will withstand a current of 20 A.

You can estimate the load capacity of a stranded wire without measuring the diameter of an individual conductor by measuring the total diameter of all twisted wires. But since the wires are round, there are air gaps between them. To eliminate the gap area, you need to multiply the result of the wire cross-section obtained from the formula by a factor of 0.91. When measuring the diameter, you need to make sure that the stranded wire does not flatten.

Let's look at an example. As a result of measurements, the stranded wire has a diameter of 2.0 mm. Let's calculate its cross-section: 2.0 mm × 2.0 mm × 0.785 × 0.91 = 2.9 mm2. Using the table (see below), we determine that this stranded wire will withstand a current of up to 20 A.

Design features of VVG 5x6

The table below shows the design features of the cable.

Characteristic nameUnit change Meaning
Number of coresPC.5
Maximum core diametermm2.9
Cable outer diameter, 0.66 kVmm15
Cable outer diameter, 1 kVmm16.5
Weight Limitkg/m0.516
Core materialCopper
Insulation materialPVC
Shell materialPVC
Core construction typeOK

Core design options:

  • ok - single-wire core;
  • mk - multi-wire core.

Undersized wire cross-section - what is the danger?

So, let's consider the dangers that await us when using low-quality wires in everyday life. It is clear that the current characteristics of current-carrying conductors decrease in direct proportion to the decrease in their cross-section. The load capacity of the wire decreases due to the reduced cross-section. According to the standards, the current that the wire can pass through is calculated. It will not collapse if less current passes through it.

The resistance between the cores decreases if the insulation layer is thinner than required. Then, in an emergency situation, when the supply voltage increases, a breakdown may occur in the insulation. If, along with this, the core itself has a reduced cross-section, that is, it cannot pass the current that, according to standards, it should pass, the thin insulation begins to gradually melt.

All these factors will inevitably lead to a short circuit and then to a fire. A fire occurs from sparks that appear during a short circuit. Let me give you an example: a three-core copper wire (for example, with a cross-section of 2.5 2), according to regulatory documentation, can pass 27 A for a long time, usually 25 A is considered.

But the wires that come into my hands, produced in accordance with the specifications, actually have a cross-section from 1.8 mm2 to 2 mm2 (this is with the declared 2.5 mm2). Based on the regulatory documentation, a wire with a cross-section of 2 mm2 can carry a current of 19 A for a long time.

Therefore, if a situation occurs when a current designed for such a cross-section flows through the wire you have chosen, which supposedly has a cross-section of 2.5 mm2, the wire will overheat. And with prolonged exposure, the insulation will melt, followed by a short circuit.

Contact connections (for example, in a socket) will collapse very quickly if such overloads occur regularly. Therefore, the socket itself, as well as the plugs of household appliances, may also be subject to melting.

Now imagine the consequences of all this! It’s especially disappointing when a beautiful renovation has been made, new appliances have been installed, for example, an air conditioner, an electric oven, a hob, a washing machine, an electric kettle, a microwave oven. And so you put the buns in the oven to bake, started the washing machine, turned on the kettle, and even the air conditioner, since it became hot.

These switched on devices are enough to cause smoke to come out of junction boxes and sockets. Then you will hear a pop, which is accompanied by a flash. And after that the electricity will disappear. It will still end well if you have circuit breakers.

What if they are of low quality? Then you won't get away with a bang and a flash. A fire will start, accompanied by sparks from the wiring burning in the wall. The wiring will burn in any case, even if it is tightly walled under the tile.

The picture I described makes it clear how responsibly you need to choose wires. After all, you will use them in your home. This is what it means to follow not GOSTs, but TUs.

Calculation of the cross-section of electrical wiring according to the power of connected electrical appliances

To select the cross-section of cable wire cores when laying electrical wiring in an apartment or house, you need to analyze the fleet of existing electrical household appliances from the point of view of their simultaneous use. The table provides a list of popular household electrical appliances indicating the current consumption depending on the power.

You can find out the power consumption of your models yourself from the labels on the products themselves or data sheets; often the parameters are indicated on the packaging. If the current consumed by an electrical appliance is not known, it can be measured using an ammeter.

Table of power consumption and current for household electrical appliances at a supply voltage of 220 V

Typically, the power consumption of electrical appliances is indicated on the housing in watts (W or VA) or kilowatts (kW or kVA). 1 kW=1000 W.

Table of power/current consumption of household electrical appliances

electrical appliancePower consumption, WCurrent strength, A
Washing machine2000 – 25009,0 – 11,4
Jacuzzi2000 – 25009,0 – 11,4
Electric floor heating800 – 14003,6 – 6,4
Stationary electric stove4500 – 850020,5 – 38,6
microwave900 – 13004,1 – 5,9
Dishwasher2000 – 25009,0 – 11,4
Freezers, refrigerators140 – 3000,6 – 1,4
Electric meat grinder1100 – 12005,0 – 5,5
Electric kettle1850 – 20008,4 – 9,0
Electric coffee maker630 – 12003,0 – 5,5
Juicer240 – 3601,1 – 1,6
Toaster640 – 11002,9 – 5,0
Mixer250 – 4001,1 – 1,8
Hairdryer400 – 16001,8 – 7,3
Iron900 –17004,1 – 7,7
Vacuum cleaner680 – 14003,1 – 6,4
Fan250 – 4001,0 – 1,8
TV125 – 1800,6 – 0,8
Radio equipment70 – 1000,3 – 0,5
Lighting devices20 – 1000,1 – 0,4

Current is also consumed by the refrigerator, lighting fixtures, radiotelephone, chargers, and TV in standby mode. But in total this power is no more than 100 W and can be ignored in calculations.

If you turn on all the electrical appliances in the house at the same time, you will need to select a wire cross-section capable of passing a current of 160 A. You will need a finger-thick wire! But such a case is unlikely. It’s hard to imagine that someone is capable of grinding meat, ironing, vacuuming and drying hair at the same time.

Calculation example. You got up in the morning, turned on the electric kettle, microwave, toaster and coffee maker. The current consumption will accordingly be:

7 A + 8 A + 3 A + 4 A = 22 A

Taking into account the switched on lighting, refrigerator and, in addition, for example, a TV, the current consumption can reach 25 A.

Selecting a wire cross-section for connecting electrical appliances to a three-phase 380 V network

When operating electrical appliances, for example, an electric motor, connected to a three-phase network, the consumed current no longer flows through two wires, but through three and, therefore, the amount of current flowing in each individual wire is somewhat less. This allows you to use a smaller cross-section wire to connect electrical appliances to a three-phase network.

To connect electrical appliances to a three-phase network with a voltage of 380 V, for example an electric motor, the wire cross-section for each phase is taken 1.75 times less than for connecting to a single-phase 220 V network. Attention, when choosing the wire cross-section for connecting an electric motor by power, you should take into account that The motor nameplate indicates the maximum mechanical power that the motor can produce at the shaft, not the electrical power consumed.

The electrical power consumed by the electric motor, taking into account efficiency and cos φ, is approximately two times greater than that created on the shaft, which must be taken into account when choosing the wire cross-section based on the motor power indicated on the plate.

For example, you need to connect an electric motor that consumes power from a 2.0 kW network. The total current consumption of an electric motor of such power in three phases is 5.2 A. According to the table, it turns out that a wire with a cross-section of 1.0 mm2 is needed, taking into account the above 1.0 / 1.75 = 0.5 mm2. Therefore, to connect a 2.0 kW electric motor to a three-phase 380 V network, you will need a three-core copper cable with a cross-section of each core of 0.5 mm2.

It is much easier to choose the wire cross-section for connecting a three-phase motor based on the current consumption, which is always indicated on the nameplate. For example, the current consumption of a 0.25 kW motor for each phase at a supply voltage of 220 V (the motor windings are connected in a delta configuration) is 1.2 A, and at a voltage of 380 V (the motor windings are connected in a star configuration) it is only 0.7 A.

Taking the current strength indicated on the nameplate, according to the table for selecting the wire cross-section for apartment electrical wiring, we select a wire with a cross-section of 0.35 mm2 when connecting the electric motor windings in a “triangle” pattern or 0.15 mm2 when connecting in a “star” pattern.

Table - diameter and weight of VVG cable

PUE 2.1.61. In boxes (cable tray + cover), wires and cables can be laid in multi-layers with an ordered and random (scattered) mutual arrangement. The sum of the cross-sections of wires and cables, calculated by their outer diameters, including insulation and outer sheaths, should not exceed: for blind boxes (non-perforated tray + cover) 35% of the clear cross-section of the box; for boxes with openable lids 40%.

It is advisable to use these conditions as a guide when calculating and selecting the size of cable pipes, metal trays, plastic boxes or to calculate the cost of delivery of cable products.

External diameter and weight of VVG cable

  • single-core
  • two-wire
  • three-core
  • four-wire
  • five-core
Number and nominal cross-section of cores, mm2 Cable outer diameter, mm Weight of 1 km cable, kg
0.66 kV 1 kV 0.66 kV 1 kV
VVG brand cables with round cores
1×1,5 5,0 5,4 39 44
1×2,5 5,4 5,8 50 55
1×4 6,0 6,6 70 78
1×6 6,5 7,1 91 99
1×10 7,8 8,0 140 143
1×16 9,9 10,1 224 229
1×25 11,0 11,2 321 327
1×35 12,0 12,2 418 423
1×50 13,5 13,7 550 556
1×70 15,2 765
1×95 17,3 1028
1×120 19,2 1279
1×150 22,2 1595
1×185 24,7 1993
1×240 27,7 2573
2×1,5 7,6 8,4 72 81
2×2,5 8,3 9,7 94 117
2×4 10,3 11,5 147 165
Number and nominal cross-section of cores, mm2 Cable outer diameter, mm Weight of 1 km cable, kg
0.66 kV 1 kV 0.66 kV 1 kV
2×6 11,3 12,5 191 210
2×10 13,7 14,1 293 300
2×16 16,7 16,7 442 449
2×25 19,4 19,8 657 667
2×35 21,4 21,8 854 865
2×50 24,8 25,2 1146 1160
2×70 28,2 1587
2×95 32,4 2127
2×120 35,8 2638
2×150 41,8 3288
3×1,5 8,0 9,5 93 117
3×2,5 9,4 10,3 137 151
3×4 10,8 12,1 194 218
3×6 11,9 13,2 257 282
3×10 14,5 14,9 403 413
3×16 17,8 17,8 619 928
3×25 20,6 21,0 926 941
3×35 22,7 23,2 1203 1232
3×50 26,4 26,8 1635 1653
3×4+1×2,5 11,8 12,8 229 253
3×6+1×4 13,0 14,4 308 339
3×10+1×6 15,4 16,4 471 490
Number and nominal cross-section of cores, mm2 Cable outer diameter, mm Weight of 1 km cable, kg
0.66 kV 1 kV 0.66 kV 1 kV
3×16+1×10 19,3 19,3 749 761
3×25+1×10 21,2 21,7 1037 1054
3×25+1×16 22,7 23,2 1112 1130
3×35+1×16 24,6 25,1 1418 1438
3×50+1×16 27,2 27,7 1811 1833
3×50+1×25 28,1 28,5 1909 1932
3×70+1×25 31,0 2557
3×95+1×35 36,1 3476
3×120+1×35 39,9 4188
3×150+1×50 46,6 5307
4×1,5 9,3 10,2 128 143
4×2,5 10,2 11,1 170 187
4×4 11,8 13,2 244 274
4×6 13,0 14,4 326 358
4×10 15,9 16,4 518 530
4×16 20,0 20,4 818 835
4x25 22,7 23,2 1203 1222
4×35 25,5 26,0 1607 1629
4×50 29,1 29,6 2133 2157
5×1,5 10,1 11,1 156 175
VVG 5x2.5 11,0 12,1 208 229
Number and nominal cross-section of cores, mm2 Cable outer diameter, mm Weight of 1 km cable, kg
0.66 kV 1 kV 0.66 kV 1 kV
5×4 12,8 14,5 302 340
5×6 14,2 15,8 406 445
5×10 17,5 18,0 646 661
5×16 22,0 22,5 1024 1041
5×25 25,4 25,9 1535 1559
5×35 28,1 28,6 2019 2045
5×50 32,2 32,7 2692 2722
5×70 37,1 3812
5×95 42,8 5154
5×120 47,3 6389
5×150 55,8 8056

Author: MEGA CABLE

© 2009-2018, Online store VSE-E.COM, Kyiv, Ukraine. All rights reserved.

vse-e.com

Cable cross-section by diameter table

Knowing the diameter of the wire, you can determine its cross-section using a ready-made dependence table. The table for calculating the cable cross-section by core diameter looks like this:

Table of cross-section versus diameter

Conductor diameter, mmConductor cross-section, mm2
0,80,5
10,75
1,11
1,.21,2
1,.41,5
1,62
1,82,5
23
2,34
2,55
2,.86
3,28
3,610
4,516

Nomenclature of cable brand VVGng-LS:

VVGng-LS 1x1.5

VVGng-LS 1x10

VVGng-LS 1x120

VVGng-LS 1x150

VVGng-LS 1x16

VVGng-LS 1x185

VVGng-LS 1x2.5

VVGng-LS 1x240

VVGng-LS 1x25

VVGng-LS 1x35

VVGng-LS 1x4

VVGng-LS 1x50

VVGng-LS 1x6

VVGng-LS 1x70

VVGng-LS 1x95

VVGng-LS 2x1.5

VVGng-LS 2x1.5+1x1

VVGng-LS 2x10

VVGng-LS 2x10+1x10

VVGng-LS 2x10+1x4

VVGng-LS 2x10+1x6

VVGng-LS 2x16

VVGng-LS 2x16+1x10

VVGng-LS 2x16+1x6

VVGng-LS 2x2.5

VVGng-LS 2x2.5+1x1.5

VVGng-LS 2x25

VVGng-LS 2x25+1x10

VVGng-LS 2x25+1x16

VVGng-LS 2x35

VVGng-LS 2x35+1x16

VVGng-LS 2x4

VVGng-LS 2x4+1x2.5

VVGng-LS 2x50

VVGng-LS 2x50+1x16

VVGng-LS 2x50+1x25

VVGng-LS 2x6

VVGng-LS 2x6+1x2.5

VVGng-LS 2x6+1x4

VVGng-LS 3x1.5

VVGng-LS 3x1.5+1x1

VVGng-LS 3x10

VVGng-LS 3x10+1x4

VVGng-LS 3x10+1x6

VVGng-LS 3x120

VVGng-LS 3x120+1x70

VVGng-LS 3x150

VVGng-LS 3x150+1x70

VVGng-LS 3x16

VVGng-LS 3x16+1x10

VVGng-LS 3x16+1x6

VVGng-LS 3x2.5

VVGng-LS 3x2.5+1x1.5

VVGng-LS 3x25

VVGng-LS 3x25+1x10

VVGng-LS 3x25+1x16

VVGng-LS 3x35

VVGng-LS 3x35+1x16

VVGng-LS 3x4

VVGng-LS 3x4+1x2.5

VVGng-LS 3x50

VVGng-LS 3x50+1x16

VVGng-LS 3x50+1x25

VVGng-LS 3x6

VVGng-LS 3x6+1x2.5

VVGng-LS 3x6+1x4

VVGng-LS 3x70

VVGng-LS 3x95

VVGng-LS 3x95+1x50

VVGng-LS 4x1.5

VVGng-LS 4x1.5+1x1

VVGng-LS 4x10

VVGng-LS 4x10+1x4

VVGng-LS 4x10+1x6

VVGng-LS 4x120

VVGng-LS 4x150

VVGng-LS 4x16

VVGng-LS 4x16+1x10

VVGng-LS 4x16+1x6

VVGng-LS 4x2.5

VVGng-LS 4x2.5+1x1.5

VVGng-LS 4x25

VVGng-LS 4x25+1x10

VVGng-LS 4x25+1x16

VVGng-LS 4x35

VVGng-LS 4x4

VVGng-LS 4x4+1x2.5

VVGng-LS 4x50

VVGng-LS 4x6

VVGng-LS 4x6+1x2.5

VVGng-LS 4x6+1x4

VVGng-LS 4x70

VVGng-LS 4x95

VVGng-LS 5x1.5

VVGng-LS 5x10

VVGng-LS 5x16

VVGng-LS 5x2.5

VVGng-LS 5x25

VVGng-LS 5x4

VVGng-LS 5x6

Wire cross-section and power table

When the cross-section is known, it is possible to determine the permissible power and current values ​​for copper or aluminum wire. In this way, it will be possible to find out what load parameters the current-carrying core is designed for. To do this, you will need a table of the dependence of the cross section on the maximum current and power.

Table of power and current values ​​from the cross-section for hidden wiring with a single-phase 220 V connection diagram

Wire core cross-section, mm2Conductor core diameter, mmCopper conductorsAluminum conductors
Current, APower, WCurrent, APower, W
0.50.861300
0.750.98102200
11.13143100
1.51.38153300102200
21.6194200143100
2.51.78214600163500
42.26275900214600
62.76347500265700
103.575011000388400
164.5180176005512100
255.64100220006514300

As we can see from the table, the cross-section of the cores depends, in addition to the load, on the material from which the wire is made.

Table of power and current values ​​from the cross-section for hidden wiring with a three-phase connection diagram of 380 V

Wire core cross-section, mm2Conductor core diameter, mmCopper conductorsAluminum conductors
Current, APower, WCurrent, APower, W
0.50.862250
0.750.98103800
11.13145300
1.51.38155700103800
21.6197200145300
2.51.78217900166000
42.262710000217900
62.763412000269800
103.5750190003814000
164.5180300005520000
255.64100380006524000

Cable diameters KG

home >
Cable diameters KG

Main technical and operational characteristics of the KG cable

Ambient temperature during cable operationfrom -40°С to +50°С for KG cables, from -30°С for cables of the KGN and KGNT brands
Relative air humidity (at temperature +35°C)98%
Minimum cable laying temperature without preheating-15°С
Limit long-term permissible operating temperature of the coresKG and KGN +75°С, for KGNT +85°С
Maximum core heating temperature during a short circuit200°С (1 sec.)
Number of short circuit cyclesNo more than 10
Electrical insulation resistancenot less than 100 MOhm.km
AC test voltage2.5 kV
Minimum permissible bending radius when layingat least 3 outer cable diameters with no more than 2 bends
Service life, not lessKG - 4 years, KGN and KGNT - 2.5 years
Warranty life of the cable6 months from the date of commissioning, but no later than 12 months from the date of manufacture

Tabular data

Number and nominal cross-section of cores, mm2Nominal outer diameter of cable, mmEstimated weight of 1 km of cable, kg
2x0.758.290
2x0.75+1x0.758.9110
3x0.758.9110
2x1.0+1x19.1100
2x1.08.5100
3x1.09.1120
4x1.010.1150
5x1.011.1190
2x1.59.4130
2x1.5+1x1.510.1160
3x1.510.1160
4x1.511.1200
5x1.512.2240
1x2.56.780
2x2.511.2190
2x2.5+1x1.511.8220
3x2.512.0230
3x2.5+1x1.513.2280
4x2.513.3290
5x2.514.6350
1x48.0110
2x413.5280
2x4+1x2.513.9310
3x414.5350
3x4+1x2.515.5400
4x416.0420
5x417.8530
1x69.0150
2x615.5380
2x6+1x416.3440
3x616.6460
3x6+1x418.0560
4x618.5590
5x620.2720
1x1011.1230
2x1021.1680
2x10+1x621.0740
3x1022.3840
3x10+1x623.5950
4x1024.41000
5x1026.81250
1x1612.4310
2x1623.7920
2x16+1x625.01070
3x1625.41130
3x16+1x627.61300
4x1627.81400
5x1630.91700
1x2514.6450
2x2528.41340
2x25+1x1030.01550
3x2530.41660
3x25+1x1033.11950
4x2533.72100
5x2537.42600
1x3516.4590
2x3531.21680
2x35+1x1032.41890
3x3534.02150
3x35+1x1036.52400
4x3537.72730
5x3544.53440
1x5019.0820
2x5038.02450
2x50+1x1637.92600
3x5039.52970
3x50+1x1642.43400
4x5043.83700
5x5050.14580
1x7021.51090
2x7042.23170
2x70+1x2542.73400
3x7044.73930
3x70+1x2547.74500
4x7049.75000
5x7054.95920
1x9524.31400
2x9547.44040
2x95+1x3548.64500
3x9550.95100
3x95+1x3554.55890
4x9556.66500
5x9563.37820
1x12027.71730
2x12050.74800
2x120+1x3554.45880
3x12054.46150
3x120+1x3560.97280
4x12062.08120
5x12067.09360
1x15030.12070
2x15057.56050
2x150+1x5058.16590
3x15063.07870
3x150+1x5064.98630
4x15069.29880
1x18532.72490
1x24036.83190
1x30040.13910
1x40043.44980

Parallel connection of electrical wiring wires

There are hopeless situations when you urgently need to lay wiring, but there is no wire of the required cross-section available. In this case, if there is a wire with a smaller cross-section than necessary, then the wiring can be made from two or more wires, connecting them in parallel. The main thing is that the sum of the sections of each of them is not less than the calculated one.

For example, there are three wires with a cross section of 2, 3 and 5 mm2, but according to calculations, 10 mm2 is needed. Connect them all in parallel and the wiring will handle up to 50 amps. Yes, you yourself have repeatedly seen the parallel connection of a large number of thin conductors to transmit large currents.

For example, welding uses a current of up to 150 A and in order for the welder to control the electrode, a flexible wire is needed. It is made from hundreds of thin copper wires connected in parallel. In a car, the battery is also connected to the on-board network using the same flexible stranded wire, since when starting the engine, the starter consumes a current of up to 100 A from the battery.

And when installing and removing the battery, it is necessary to move the wires to the side, that is, the wire must be flexible enough. The method of increasing the cross-section of an electrical wire by connecting several wires of different diameters in parallel can be used only as a last resort. When laying home electrical wiring, it is permissible to connect in parallel only wires of the same cross-section taken from the same reel.

Author: Sergey Vladimirovich, electrical engineer. More about the author.

Correspondence of electric diameters cables and corrugated pipes

When laying corrugated pipes, sharp corners should be avoided, as well as close proximity of several corners. The working distance for pulling the wire in the pipe is 20-25 m with a maximum number of correctly laid out 4-5 corners. If it is necessary to increase the length of a solid piece of pipe and the number of corners, transit boxes should be installed at the corners or in places close to the middle of the solid piece of pipe. Pulling several networks simultaneously in one pipe is unacceptable. The laying of each type of communications is carried out in its own pipes and boxes intended only for these purposes at a certain distance from each other. In monolithic construction, corrugated pipes of the heavy series are laid before the mortar is supplied and fixed to the load-bearing metal structures; the wire is pulled after the wall has already been formed.

  • Table of correspondence between the sizes of VVG cable and corrugated pipes, rigid pipes, metal hoses.
Cable nameRigid pipeMetalsleeveCorrugated pipe
Cable VVG 2x1.5Rigid pipe 20Metal hose 15PVC corrugated pipe 20
Cable VVG 2x2.5Rigid pipe 20Metal hose 18PVC corrugated pipe 25
Cable VVG 2x4Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable VVG 2x6Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable VVG 2x10Rigid pipe 32Metal hose 25PVC corrugated pipe 32
Cable VVG 3x1.5Rigid pipe 20Metal hose 15PVC corrugated pipe 20
Cable BBГ 3x2.5Rigid pipe 20Metal hose 18PVC corrugated pipe 25
Cable VVG 3x4Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable VVG 3x6Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable VVG 3x10Rigid pipe 32Metal hose 32PVC corrugated pipe 40
Cable VVG 4x1.5Rigid pipe 20Metal hose 18PVC corrugated pipe 25
Cable VVG 4x2.5Rigid pipe 25Metal hose 18PVC corrugated pipe 25
Cable VVG 4x4Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable VVG 4x6Rigid pipe 32Metal hose 25PVC corrugated pipe 32
Cable VVG 4x10Rigid pipe 32Metal hose 32PVC corrugated pipe 40
Cable VVG 4x16Rigid pipe 40Metal hose 38Corrugated pipe PVC 50
Cable VVG 4x25Rigid pipe 50Metal hose 50
Cable VVG 4x35Rigid pipe 63Metal hose 50
Cable VVG 4x50Rigid pipe 63Metal hose 63
Cable VVG 5x1.5Rigid pipe 25Metal hose 18PVC corrugated pipe 25
Cable VVG 5x2.5Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable VVG 5x4Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable VVG 5x6Rigid pipe 32Metal hose 32PVC corrugated pipe 40
Cable VVG 5x10Rigid pipe 40Metal hose 38Corrugated pipe PVC 50
Cable VVG 5x16Rigid pipe 50Metal hose 50Corrugated pipe PVC 50
Cable VVG 5x25Rigid pipe 50Metal hose 50
Cable VVG 5x35Rigid pipe 63Metal hose 63
Cable VVG 5x50Rigid pipe 63Metal hose 80
  • Table of correspondence between the sizes of AVVG cable and corrugated pipes, rigid pipes, metal hoses.
Cable nameRigid pipeMetalsleeveCorrugated pipe
Cable AVVG 2x2.5Rigid pipe 20Metal hose 18PVC corrugated pipe 25
Cable AVVG 2x4Rigid pipe 20Metal hose 18PVC corrugated pipe 25
Cable AVVG 2x6Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable AVVG 2x10Rigid pipe 32Metal hose 25PVC corrugated pipe 32
Cable AVVG 2x16Rigid pipe 32Metal hose 32PVC corrugated pipe 40
Cable AVVG 3x2.5Rigid pipe 20Metal hose 18PVC corrugated pipe 25
Cable AVVG 3x4Rigid pipe 25Metal hose 18PVC corrugated pipe 25
Cable AVVG 3x6Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable AVVG 3x10Rigid pipe 32Metal hose 25PVC corrugated pipe 32
Cable AVVG 3x16Rigid pipe 40Metal hose 38Corrugated pipe PVC 50
Cable AVVG 3x4+1x2.5Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable AVVG 3x6+1x4Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable AVVG 3x10+1x6Rigid pipe 32Metal hose 32PVC corrugated pipe 40
Cable AVVG 3x16+1x10Rigid pipe 40Metal hose 32PVC corrugated pipe 40
Cable AVVG 3x25+1x16Rigid pipe 50Metal hose 38Corrugated pipe PVC 50
Cable AVVG 3x35+1x16Rigid pipe 50Metal hose 50
Cable AVVG 3x50+1x25Rigid pipe 63Metal hose 50
Cable AVVG 3x70+1x35Rigid pipe 63Metal hose 63
Cable AVVG 3x95+1x50Metal hose 63
Cable AVVG 3x120+1x70Metal hose 80
Cable AVVG 4x2.5Rigid pipe 25Metal hose 18PVC corrugated pipe 25
Cable AVVG 4x4Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable AVVG 4x6Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Cable AVVG 4x10Rigid pipe 32Metal hose 32PVC corrugated pipe 40
Cable AVVG 4x16Rigid pipe 40Metal hose 32PVC corrugated pipe 40
Cable AVVG 4x25Rigid pipe 40Metal hose 38Corrugated pipe PVC 50
Cable AVVG 4x35Rigid pipe 50Metal hose 50
Cable AVVG 4x50Rigid pipe 63Metal hose 63
Cable AVVG 4x70Rigid pipe 63Metal hose 63
Cable AVVG 4x95Metal hose 80
Cable AVVG 4x120Metal hose 80
  • Table of correspondence between the sizes of PVA wire and corrugated pipes, rigid pipes, metal hoses.
Cable nameRigid pipeMetalsleeveCorrugated pipe
Wire PVS 2x0.5Rigid pipe 16Metal sleeve 10PVC corrugated pipe 16
Wire PVS 2x0.75Rigid pipe 16Metal hose 12PVC corrugated pipe 16
PVS wire 2x1Rigid pipe 16Metal hose 12PVC corrugated pipe 20
Wire PVS 2x1.5Rigid pipe 16Metal hose 15PVC corrugated pipe 20
Wire PVS 2x2.5Rigid pipe 20Metal hose 18PVC corrugated pipe 25
PVS wire 2x4Rigid pipe 25Metal hose 25PVC corrugated pipe 32
PVS wire 2x6Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Wire PVS 3x0.5Rigid pipe 16Metal hose 12PVC corrugated pipe 16
Wire PVS 3x0.75Rigid pipe 16Metal hose 12PVC corrugated pipe 20
Wire PVS 3x1Rigid pipe 16Metal hose 12PVC corrugated pipe 20
Wire PVS 3x1.5Rigid pipe 20Metal hose 15PVC corrugated pipe 20
Wire PVS 3x2.5Rigid pipe 20Metal hose 18PVC corrugated pipe 25
PVS wire 3x4Rigid pipe 25Metal hose 25PVC corrugated pipe 32
PVS wire 3x6Rigid pipe 32Metal hose 25PVC corrugated pipe 32
Wire PVS 4x0.5Rigid pipe 16Metal sleeve 10PVC corrugated pipe 16
Wire PVS 4x0.75Rigid pipe 16Metal hose 12PVC corrugated pipe 16
Wire PVS 4x1Rigid pipe 16Metal hose 12PVC corrugated pipe 20
Wire PVS 4x1.5Rigid pipe 20Metal hose 15PVC corrugated pipe 20
Wire PVS 4x2.5Rigid pipe 20Metal hose 18PVC corrugated pipe 25
PVS wire 4x4Rigid pipe 25Metal hose 25PVC corrugated pipe 32
PVS wire 4x6Rigid pipe 32Metal hose 25PVC corrugated pipe 32
Wire PVS 5x0.5Rigid pipe 16Metal hose 12PVC corrugated pipe 16
Wire PVS 5x0.75Rigid pipe 16Metal hose 12PVC corrugated pipe 20
Wire PVS 5x1Rigid pipe 16Metal hose 12PVC corrugated pipe 20
Wire PVS 5x1.5Rigid pipe 20Metal hose 15PVC corrugated pipe 20
Wire PVS 5x2.5Rigid pipe 20Metal hose 18PVC corrugated pipe 25
PVS wire 5x4Rigid pipe 25Metal hose 25PVC corrugated pipe 32
PVS wire 5x6Rigid pipe 32Metal hose 25PVC corrugated pipe 32
  • Table of correspondence between the sizes of ball screw wires and corrugated pipes, rigid pipes, metal hoses.
Cable nameRigid pipeMetalsleeveCorrugated pipe
Wire SHVVP 2x0.5Rigid pipe 16Metal sleeve 10PVC corrugated pipe 16
Wire SHVVP 2x0.75Rigid pipe 16Metal sleeve 10PVC corrugated pipe 16
Wire SHVVP 2x1Rigid pipe 16Metal sleeve 10PVC corrugated pipe 16
Wire SHVVP 2x1.5Rigid pipe 16Metal hose 12PVC corrugated pipe 20
Wire SHVVP 2x2.5Rigid pipe 16Metal hose 15PVC corrugated pipe 20
ShVVP wire 2x4Rigid pipe 20Metal hose 15PVC corrugated pipe 25
Wire SHVVP 2x6Rigid pipe 25Metal hose 18PVC corrugated pipe 25
Wire SHVVP 3x0.5Rigid pipe 16Metal sleeve 10PVC corrugated pipe 16
Wire SHVVP 3x0.75Rigid pipe 16Metal hose 12PVC corrugated pipe 16
Wire SHVVP 3x1Rigid pipe 16Metal hose 12PVC corrugated pipe 20
Wire SHVVP 3x1.5Rigid pipe 16Metal hose 15PVC corrugated pipe 20
Wire SHVVP 3x2.5Rigid pipe 20Metal hose 15PVC corrugated pipe 25
Wire SHVVP 3x4Rigid pipe 20Metal hose 18PVC corrugated pipe 25
Wire SHVVP 3x6Rigid pipe 25Metal hose 25PVC corrugated pipe 32
Rating
( 2 ratings, average 4.5 out of 5 )
Did you like the article? Share with friends:
For any suggestions regarding the site: [email protected]
Для любых предложений по сайту: [email protected]